10
WARNING
Failure to follow all precautions could result in fire, explosion or death!

GAS CONNECTION

removing the cap and installing the manometer. The gas pressure must remain between 7" and 14"
during stand-by (static) mode and while in operating (dynamic) mode. If an in-line regulator is used,
it must be a minimum of 10 feet from the Munchkin. It is very important that the gas line is prop-
erly purged by the gas supplier or utility. Failure to properly purge the lines or improper line siz-
ing, will result in ignition failure. This problem is especially noticeable in NEW LP installations and
also in empty tank situations. This can also occur when a utility company shuts off service to an area
to provide maintenance to their lines. This gas valve must not be replaced with a conventional gas
valve under any circumstances. As an additional safety feature, this gas valve has a flanged con-
nection to the Venturi and blower.
MUNCHKIN BURNERTECH GAS VALVE
INLET PRESSURE TAP OUTLET PRESSURE TAP
THROTTLE ADJUSTER
VENTURI
110 VOLT AC ELECTRICAL CONNECTION
(NOTE: INLET GAS PRESSURE CAN
BE MEASURED TO ASSURE
PROPER GAS SUPPLY)
(NOTE: A NEGATIVE READING WILL BE
MEASURED WHILE THE FAN IS
IN OPERATION)
(NOTE: IF FOR ANY REASON THE THROTTLE
NEEDS TO BE ADJUSTED,
IT IS VERY IMPORTANT THAT A " COMBUSTION
ANALYZER " BE USED TO ENSURE SAFE AND PROPER OPERATION
TURN THE ADJUSTER TO THE (+) TO INCREASE GAS
OR TO THE (-) TO DECREASE THE GAS SUPPLY.
THIS ADJUSTMENT COULD AFFECT THE CO/CO % LEVELS.
MAKE SURE THE LEVELS CORRESPOND TO THE CHART IN
FIG. 3-2 COMBUSTION SETTINGS)
2
Fig. 3-1
Fig. 3-2
SGNITTESNOITSUBMOC
SLEDOMLLANOSETARGNIRIFWOLdnaSETARGNIRIFHGIH
saGlarutaNPLenaporP
wolhgihwolhgih
mppOCnobraC
edixonoM mpp020mpp531mpp07mpp020mpp05108
OCnobraC
%2
edixoiD %2/1-9%2/1-8%2/1-9%2/1-8%2/1-01%2/1-9%2/1-01%2/1-9