2.8 Additional Function Parameters

2.8.1 Remote setting function selection

If the operator panel is located away from the control box, you can use contact signals to perform continuous variable-speed operation, without using analog signals.

(Hz)

 

 

When Pr. 59="2"

 

 

 

When Pr. 59="1"

 

Output frequency

*

 

 

 

 

 

 

 

 

 

 

ON

 

ON

 

Acceleration(RH)

ON

 

 

 

Deceleration(RM)

ON

 

 

 

 

ON

 

 

Clear(RL)

 

 

 

 

 

 

 

Forward rotation

ON

ON

ON

ON

(STF)

 

ON

 

ON

Power supply

 

 

 

 

 

 

* External operation frequency or PU operation frequency other than at multiple speeds

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

59

Remote setting

0

0, 1, 2

Setting is enabled when Pr. 30 = "1"

function selection

 

 

 

 

REMARKS

When the remote function is used, the output frequency of the inverter can be compensated for as follows:

External operation mode

Frequency set by RH/RM operation plus external

 

analog frequency command

PU operation mode

Frequency set by RH/RM operation plus setting dial

 

or PU digital preset frequency

<Operation panel operation procedure>

Monitor, frequency

Turn setting dial to

Press SET key to

setting mode MODE

make correction.

complete setting.*

*When you have set "1" in Pr. 53 "frequency setting operation selection", you need not press the SET key.

86

Page 95
Image 95
Mitsubishi FR - S500 Additional Function Parameters, Remote setting function selection, Or PU digital preset frequency