Rated input AC (DC) voltage, frequency
Permissible AC (DC) voltage fluctuation
Permissible frequency fluctuation
Power supply system capacity (kVA) (*5)
HP
Rated capacity (kVA) (*2)
Rated current (A)
Overload capacity (*3)
Voltage (*4)

4.1 Specification List

4.1.1 Ratings

(1)3-phase 200V power supply

Japanese version

FR-S520-0.1K to 3.7K (-R) (-C) NA version

FR-S520-0.1K to 3.7K-NA

Type FR-S520-K(-R) (-C)

Applicable motor capacity kW (*1)

Power supply Output

Protective structure (JEM1030)

Cooling system

Approximate weight (kg (lbs))

0.1

0.2

0.4

0.75

1.5

2.2

3.7

0.1

0.2

0.4

0.75

1.5

2.2

3.7

1/8

1/4

1/2

1

2

3

5

0.3

0.5

1.0

1.6

2.8

4.0

6.6

0.8

1.4

2.5

4.1

7.0

10

16.5

 

 

 

 

 

 

 

150% 60s 200% 0.5s (Inverse time characteristics)

Three phase, 200V to 240V 50Hz/60Hz

Three phase, 200V to 240V 50Hz/60Hz

170 to 264V 50Hz/60Hz

±5%

0.4

0.7

1.2

2.1

4.0

5.5

9

 

 

 

 

 

 

 

Enclosed type (IP20), IP40 for dirt-protection structure series

 

Self-cooling

 

Forced air cooling

0.5

0.5

0.8

0.9

1.5

1.5

2.1

(1.1)

(1.1)

(1.76)

(1.98)

(3.3)

(3.3)

(4.62)

*1. The applicable motor capacity indicated is the maximum capacity applicable when a Mitsubishi 4-pole standard motor is used.

*2. The rated output capacity indicated assumes that the output voltage is 230V.

*3. The % value of the overload capacity indicates the ratio of the overload current to the inverter's rated output current.

For repeated duty, allow time for the inverter to return to or below the temperatures under 100% load.

*4. The maximum output voltage cannot exceed the power supply voltage. The maximum output voltage may be set as desired below the power supply voltage. However, the PWM pulse voltage value of the inverter output side voltage remains unchanged at about 2 that of the power supply.

*5. The power supply capacity changes with the values of the power supply side inverter impedances (including those of the input reactor and cables).