1.1 Japanese Version

1.1.1 Terminal connection diagram

FR-S520-0.1K to 3.7K (-R) (-C)

FR-S540-0.4K to 3.7K (-R)

 

NFB MC

Inverter

3-phase AC

R

power supply

S

T

External transistor common

 

 

24VDC power supply

PC

Contact input common (source)

 

 

 

 

 

Be careful not to short

 

 

terminals PC-SD.

 

 

 

 

 

Forward rotation start

STF

U

V

W

P1

P

N

Motor

IM

Ground

Power factor improving DC reactor (FR-BEL: Option)

Jumper: Remove this jumper when FR-BEL is connected.

Reverse rotation start

*5

 

 

 

 

 

 

 

High

*5

*6

B

Alarm

 

 

Multi-speed selection Middle

RM *5

*6

C

output

 

 

 

 

 

 

 

 

 

Low

*5

 

 

Running

 

Operation status

Contact input common

SD

 

 

 

output

 

SE

Open collector

 

 

 

(Note)

 

Open

Control input signals

SINK

 

 

output common

collector

 

 

 

 

outputs

(No voltage input allowed)

 

 

 

 

 

 

(*3)

 

 

 

 

 

 

 

 

 

 

 

 

Frequency setting signals (Analog)

SOURCE

 

Indicator

 

 

 

 

 

 

1mA full-scale

 

 

 

 

 

 

Frequency

 

3 2

10 (+5V)

 

 

Analog meter

 

Selected

 

(Digital indicator)

setting

 

 

2 DC 0 to 5V

 

 

1mA

 

potentiometer

1

DC 0 to 10V

 

FM

 

 

1/2W1k

 

5 (Common)

 

(+)

(-)

 

 

Calibration

(*4)

Current input (-)

 

 

 

 

 

 

 

 

resistor (*2)

 

 

 

 

 

 

4 to 20mADC (+)

4 (4 to 20mADC)

 

 

SD

 

 

 

 

 

 

 

 

 

 

 

When using the current input as

 

 

 

 

 

the frequency setting signal, set

 

 

 

 

 

"4" in any of Pr. 60 to Pr. 63 (input

 

 

 

 

 

RS-485 Connector (*1)

 

terminal function selection), assign

 

 

 

 

 

 

 

AU (current input selection) to any

 

 

 

 

Earth (Ground)

 

 

 

of terminals RH, RM, RL and STR,

 

 

 

 

 

 

 

 

 

and turn on the AU signal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main circuit terminal Control circuit input terminal Control circuit output terminal

REMARKS

*1 Only the type with RS-485 communication function.

*2 Not needed when the setting dial is used for calibration. This resistor is used when calibration must be made near the frequency meter for such a reason as a remote frequency meter. Note that the needle of the frequency meter may not deflect to full-scale when the calibration resistor is connected. In this case, use both the resistor and setting dial for calibration.

*3 You can switch between the sink and source logic positions. Refer to page 25. *4 When the setting potentiometer is used frequently, use a 2W1kpotentiometer. *5 The terminal functions change with input terminal function selection (Pr. 60 to

Pr. 63). (Refer to page 38, 88) (RES, RL, RM, RH, RT, AU, STOP, MRS, OH, REX, JOG, X14, X16, (STR) signal selection)

*6 The terminal functions change with output terminal function selection (Pr. 64, Pr. 65). (Refer to page 90) (RUN, SU, OL, FU, RY, Y12, Y13, FDN, FUP, RL, LF, ABC signal selection)