Mitsubishi FR - S500 Biases and gains of the frequency setting voltage current, Setting

Models: FR - S500

1 191
Download 191 pages 47.82 Kb
Page 83
Image 83

2.3.18 Biases and gains of the frequency setting voltage (current)

to

You can set the magnitude (slope) of the output frequency as desired in relation to the external frequency setting signal (0 to 5V, 0 to 10V or 4 to 20mA DC). The "bias" and "gain" functions are used to adjust the relationship between the input signal entered from outside the inverter to set the output frequency, e.g. 0 to 5VDC, 0 to 10VDC or 4 to 20mADC, and the output frequency.

60Hz<50Hz>

 

Factory setting 60Hz<50Hz>

 

 

 

Factory setting

 

( Pr.38 )

(Hz)

 

 

 

( Pr.39 )

(Hz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output frequency

 

(Across

 

Output

frequency

 

 

 

 

(Across

 

 

terminals

 

 

 

 

terminals

 

 

2-5)

 

 

 

 

 

4-5)

0Hz( C2 ) 0V

 

 

0Hz( C5 )

 

 

 

 

 

 

5V or 10V

 

 

4mA

20mA

 

(0% C3 )

(100% C4 ) Pr.73

 

(20% C6 )

(100% C7 )

 

Frequency setting voltage signal

 

 

Frequency setting current signal

 

 

 

 

 

 

 

 

 

Parameter

 

 

Name

 

Factory Setting

Setting

Remarks

 

 

 

<EC version>

 

 

 

Range

 

 

 

 

 

 

 

 

 

 

38

Frequency setting voltage gain

 

 

 

60Hz

 

 

 

 

1 to 120Hz

 

 

frequency

 

 

 

<50Hz>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

39

Frequency setting current gain

 

 

 

60Hz

 

 

 

 

1 to 120Hz

 

 

frequency

 

 

 

<50Hz>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C2 (902)

Frequency setting voltage bias

 

 

 

0Hz

 

 

 

 

0 to 60Hz

 

 

frequency

 

 

 

 

 

 

 

 

Setting is enabled

C3 (902)

Frequency setting voltage bias

 

 

 

0% *

 

 

 

 

0 to 300%

when Pr. 30 = "1".

C4 (903)

Frequency setting voltage gain

 

 

96% *

 

 

 

 

0 to 300%

 

 

C5 (904)

Frequency setting current bias

 

 

 

0Hz

 

 

 

 

0 to 60Hz

 

 

 

frequency

 

 

 

 

 

 

 

 

 

 

 

 

C6 (904)

Frequency setting current bias

 

 

20% *

 

 

 

 

0 to 300%

 

 

C7 (905)

Frequency setting current gain

 

 

100% *

 

 

 

 

0 to 300%

 

 

* Settings may differ because of calibration parameters.

The parameter numbers within parentheses are those for use of the parameter unit (FR-PU04). When the parameter unit (FR-PU04) is used, operation from the operation panel is not accepted.

 

POINT

 

 

 

 

Use calibration parameters C2, C3 for setting.

 

 

 

Bias setting for 0-5VDC (0-10VDC) input

Gain setting for 0-5VDC (0-10VDC) input

Use Pr. 38, calibration parameter C4 for

 

 

 

setting.

Bias setting for 4-20mADC input

Use calibration parameters C5, C6 for

 

 

 

setting.

Gain setting for 4-20mADC input

Use Pr. 39, calibration parameter C7 for

 

 

 

setting.

(For 4 to 20mADC input, set "4" in any of Pr. 60 to Pr. 63 (input terminal function selection) and assign AU (current input selection) to any of terminals RH, RM, RL and STR, and turn on the AU signal.)

74

Page 83
Image 83
Mitsubishi FR - S500 Biases and gains of the frequency setting voltage current, Use Pr , calibration parameter C4 for