1.6 How to Use the Control Circuit Terminals

1.6.1 Terminal block layout

In the control circuit of the inverter, the terminals are arranged as shown below:

Terminal arrangement

of control circuit

PC SE RUN 10

2

5

4

A B C

Terminal screw

size: M3

SD

SD

STF

STR

RL

RM

RH

FM

 

Japanese version

 

<AM>

 

NA, EC version

 

 

 

 

 

 

 

 

Terminal screw size: M2

REMARKS

For the cable size, wiring length, etc., refer to the instruction manual (basic).

1.6.2 Wiring instructions

1)Terminals SD, SE and 5 are common to the I/O signals. These common terminals must not be earthed.

2)Use shielded or twisted cables for connection to the control circuit terminals and run them away from the main and power circuits (including the 200V relay sequence circuit).

3)The input signals to the control circuit are micro currents. When contacts are required, use two or more parallel micro signal contacts or a twin contact to prevent a contact fault.

*Information on bar terminals

Introduced products (as of June, 2000): Phoenix Contact Co.,Ltd.

 

 

Bar Terminal Model

Bar Terminal Model

Wire Size (mm2)

Terminal Screw Size

(With Insulation

(Without Insulation

 

 

Sleeve)

Sleeve)

 

M3 (A, B, C terminals)

 

Al 0.5-6WH

A 0.5-6

0.3 to 0.5

 

Al 0.75-6GY

A 0.75-6

0.5 to 0.75

 

 

M2

 

Al 0.5-6WH

A 0.5-6

0.3 to 0.5

(Other than the above)

 

 

 

 

 

Bar terminal crimping terminal: CRIMPFOX ZA3 (Phoenix Contact Co., Ltd.)

CAUTION

When using the bar terminal (without insulation sleeve), use care so that the twisted wires do not come out.

24

Page 33
Image 33
Mitsubishi FR - S500 How to Use the Control Circuit Terminals, Terminal block layout, M3 A, B, C terminals Al 0.5-6WH