Mitsubishi FR - S500 Insulation resistance test using megger, Pressure test, Interval Daily

Models: FR - S500

1 191
Download 191 pages 47.82 Kb
Page 159
Image 159

3.3.4 Insulation resistance test using megger

1)Before performing the insulation resistance test using a megger on the external circuit, disconnect the cables from all terminals of the inverter so that the test voltage is not applied to the inverter.

2)For the continuity test of the control circuit, use a meter (high resistance range) and do not use the megger or buzzer.

3)For the inverter, conduct the insulation resistance test on the main circuit only as shown below and do not perform the test on the control circuit. (Use a 500VDC megger.)

 

 

 

 

 

 

 

R

Inverter U

 

 

 

Motor

Power supply

 

 

IM

S

 

 

 

 

V

 

 

500VDC

T

 

 

 

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

megger

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Earth terminal

3.3.5 Pressure test

Do not conduct a pressure test. The inverter may be deteriorated.

3.3.6 Daily and periodic inspection

Areaof Inspection

 

 

 

 

Interval

 

 

 

 

 

Daily

year1

years2

 

 

 

 

Inspection

 

 

 

 

 

 

Periodic*

 

 

 

 

Item

Description

 

 

 

 

 

 

 

Method

Criterion

Instrument

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Make

Ambient

Thermo-

 

 

 

 

 

 

 

 

 

 

measurement

temperature:

meter,

 

 

Check ambient

 

 

 

 

 

 

 

5cm (1.97inches)

-10ºC to +50ºC

hygrometer,

 

 

 

 

 

 

 

 

 

away from

(14ºF to 122ºF),

recorder

 

Surrounding

temperature,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inverter.

non-freezing.

 

 

environment

humidity, dust,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ambient

 

 

 

 

 

 

 

 

 

 

 

 

 

dirt, etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

humidity: 90%

 

 

 

 

 

 

 

 

 

 

 

 

 

General

 

 

 

 

 

 

 

 

 

 

or less, non-

 

 

 

 

 

 

 

 

 

 

 

condensing.

 

 

Check for

 

 

 

 

 

 

 

Visual and

No fault.

 

Overall unit

unusual

 

 

 

 

 

 

 

auditory checks.

 

 

 

 

 

 

 

 

 

 

 

 

vibration and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

noise.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Measure voltage

Within

Meter, digital

 

Power

Check that main

 

 

 

 

 

 

 

across inverter

permissible AC

multimeter

 

 

 

 

 

 

 

 

terminals R-S-T

(DC) voltage

 

 

supply

circuit voltage is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fluctuation

 

 

 

 

 

 

 

 

 

 

 

 

voltage

normal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Refer to page

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

161)

 

3

150

Page 159
Image 159
Mitsubishi FR - S500 Insulation resistance test using megger, Pressure test, Daily and periodic inspection, Interval Daily