2.10 Operation Selection Function Parameters

2.10.1 Retry function

When any protective function (major fault) is activated and the inverter stops its output, the inverter itself resets automatically and performs retries. You can select whether retry is made or not, alarms reset for retry, number of retries made, and waiting time.

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

66

Retry selection

0

0 to 3

 

 

Number of

 

0, 1 to

 

67

retries at alarm

0

10, 101

 

 

occurrence

 

to 110

Setting is enabled when Pr. 30 = "1"

68

Retry waiting

1s

0.1 to

 

time

360s

 

 

 

 

69

Retry count

0

0

 

display erase

 

 

 

 

 

<Setting>

Use Pr. 66 to choose the protective functions (major failures) for retries.

Pr. 66 Setting

 

 

Protective Functions (Major Failures) for Retries

 

 

OCT

OVT

THM THT

FIN

GF

OHT OLT

PE

PUE RET

CPU

OPT

0

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

* Indicates the retry items selected. (OCT denotes any of OC1 to OC3 and OVT any of OV1 to OV3.)

Use Pr. 67 to set the number of retries at alarm occurrence.

Pr. 67 Setting

Number of Retries

Alarm Signal Output

0

Retry is not made.

———

1 to 10

 

1 to 10 times

Not output every time *

101 to 110

 

1 to 10 times

Output every time

* If the retry count is exceeded, "

" (retry count excess) is displayed.

Use Pr. 68 to set the waiting time from when an inverter alarm occurs until a restart in the range 0.1 to 360s.

Reading the Pr. 69 value provides the cumulative number of successful restart times made by retry. The setting of "0" erases the cumulative number of times.