CAUTION

Do not reset the inverter with the start signal on.

Otherwise, the motor will start instantly after resetting, leading to potentially hazardous conditions.

2.10.7 Cooling fan operation selection

You can control the operation of the cooling fan built in the inverter (whether there is a cooling fan or not depends on the model.).

Parameter

Name

Factory

Setting

Remarks

 

Setting

Range

 

 

 

 

 

 

Cooling fan

 

 

0: Operation is performed with

Setting is

76

operation

1

0, 1

power on.

enabled when

 

selection

 

 

1: Cooling fan ON/OFF control

Pr. 30 = "1"

<Setting>

Setting

Description

0Operated at power on (independent of whether the inverter is running or at a stop). Cooling fan ON/OFF control valid

Always on during inverter operation

1 During stop (reset or error), the inverter status is monitored and the fan is switched on/off according to the temperature.

Heat sink temperature is less than 40ºC (104ºF) ..............Cooling fan off

Heat sink temperature is not less than 40ºC (104ºF) ........Cooling fan on

REMARKS

In either of the following cases, fan operation is regarded as faulty, is shown on the control panel, and the minor fault (LF) signal is output. Use any of Pr. 64, Pr. 65 (output terminal function selection) to allocate the terminal used to output the LF signal.

Pr. 76 = "0"

When the fan comes to a stop with power on. Pr. 76 = "1"

When the inverter is running and the fan stops during fan ON command or the fan starts during fan OFF command.

CAUTION

When the terminal assignment is changed using Pr. 64, Pr. 65, the other functions may be affected. Confirm the functions of the corresponding terminals before making settings.

96