Noise reduction examples

 

 

 

FR-BLF

Control

Reduce carrier

 

 

 

 

 

 

 

 

FR-BLF

Install filter FR-BSF01

 

box

frequency.

 

 

 

 

 

 

 

 

 

 

Install filter

 

 

 

 

 

 

 

 

 

 

 

 

FR-BSF01

on inverter's input side.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on inverter's output side.

Inverter

 

 

FR-

 

 

 

 

 

 

 

 

 

 

 

 

 

FR-

 

 

 

 

 

 

 

Inverter

 

 

 

 

 

 

 

 

 

 

 

IM Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLF

 

 

 

 

 

BLF

 

 

 

 

 

 

 

 

power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Install filter FR-BIF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FR-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Use 4-core cable for motor

on inverter's input side.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Separate inverter and power

 

 

 

BIF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

power cable and use one

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cable as earth cable.

line more than 30cm (3.94inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(at least 10cm (11.81inches))

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Use twisted pair shielded cable.

from sensor circuit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sensor

 

 

 

 

Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

power supply Do not earth control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

box directly.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do not earth shield but connect

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do not earth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

it to signal common cable.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

control cable.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5.8 Grounding precautions

Leakage currents flow in the inverter. To prevent an electric shock, the inverter and motor must be grounded.

Use the dedicated ground terminal to ground the inverter. (Do not use the screw in the casing, chassis, etc.)

Use a tinned* crimping terminal to connect the earth cable. When tightening the screw, be careful not to break the threads.

*Plating should not include zinc.

Use the thickest possible ground cable. Use the cable whose size is equal to or

greater than that indicated in the following table, and minimize the cable length. 1 The grounding point should be as near as possible to the inverter.

 

 

(Unit: mm2)

Motor Capacity

Ground Cable Size

200V, 100V class

400V class

 

2.2kW (3HP) or less

2 (2.5)

2 (2.5)

3.7kW (5HP)

3.5 (4)

2 (4)

For use as a product compliant with the Low Voltage Directive, use PVC cable whose size is indicated within parentheses.

Ground the motor on the inverter side using one cable of the 4-core cable.