2.11 Auxiliary Function Parameters

2.11.1 Slip compensation

The inverter output current may be used to assume motor slip to keep the motor speed constant.

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

95

Rated motor slip

- - -

0 to 50%,

 

- - -

 

 

 

 

 

96

Slip compensation time

0.5s

0.01 to 10s

Setting is enabled when

 

constant

 

 

Pr. 30 = "1"

97

Constant-output region slip

- - -

0, - - -

 

compensation selection

 

 

 

 

 

<Setting>

Rated slip =

Synchronous speed at base frequency - rated speed

×100[%]

Synchronous speed at base frequency

 

 

 

 

 

 

 

 

Parameter

 

Setting

Function

 

95

 

0.01 to 50%

Used to set the rated motor slip.

 

 

0, - - -

Slip compensation is not made.

 

 

 

 

96

 

0.01 to 10s

Used to set the slip compensation response time. (*)

 

 

0

Slip compensation is not made in the constant output

97

 

range (frequency range above the frequency set in Pr. 3).

 

 

 

 

- - -

Slip compensation is made in the constant output range.

*When this value is made smaller, response will be faster.

However, as load inertia is greater, a regenerative overvoltage (OVT) error is more liable to occur.

REMARKS

When making slip compensation at 60Hz<50Hz>, set the maximum frequency to slightly higher than 60Hz<50Hz>.

In the factory setting status, it is clamped at 60Hz<50Hz>.

2.11.2

Automatic torque boost selection

2

You can choose automatic torque boost control.

Automatic torque boost control

Not only gives the motor the optimum excitation but also provides high torque even in a low speed range.

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

98

Automatic torque boost

- - -

0.1 to 3.7kW,

Setting is enabled when

selection (motor capacity)

- - -

Pr. 30 = "1"

 

 

109