Input signals

Output signals

Communication

Symbol

Terminal Name

Description

 

Frequency

Common terminal for the frequency setting signals

5setting input (terminals 2, 4) and indicator connection (terminal AM).

 

 

 

common

Isolated from terminals SD and SE. Do not earth.

 

 

 

 

Change-over contact output indicating

 

 

 

 

 

 

A

 

 

 

that the output has been stopped by the

 

 

 

 

inverter's protective function activated.

 

B

 

 

Alarm output

230V 0.3A AC, 30V 0.3A DC. Alarm:

Output

C

 

 

 

discontinuity across B-C (continuity

 

 

 

terminal

 

 

 

 

across A-C), normal: continuity across

 

 

 

 

function

 

 

 

 

B-C (discontinuity across A-C). (*6)

 

 

 

 

selection

collector

 

 

 

Switched low when the inverter output

(Pr. 64, Pr. 65)

 

 

 

changes the

 

 

 

 

frequency is equal to or higher than the

 

 

 

 

terminal

 

 

 

 

starting frequency (factory set to 0.5Hz,

 

RUN

Inverter running

functions. (*5)

 

variable). Switched high during stop or

Open

 

 

 

 

 

 

 

DC injection brake operation. (*2)

 

 

 

 

Permissible load 24VDC 0.1A DC.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SE

 

 

Open collector

Common terminal

for inverter running

terminal RUN.

 

 

output common

Isolated from terminals 5 and SD.

 

 

 

 

 

Indicator

PulseAnalog

FMAM <Japanese>EC><NA,

 

 

 

Factory setting of output item:

 

 

 

For meter

One selected from

 

Frequency

 

 

 

 

 

Permissible load current 1mA

 

 

 

 

output frequency

 

 

 

 

 

 

1440 pulses/s at 60Hz

 

 

 

 

and motor current is

 

 

 

 

 

 

 

 

 

 

output.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The output signal is

 

Factory setting of output item:

 

 

 

Analog signal

proportional to the

 

 

 

 

magnitude of each

 

Frequency

 

 

 

 

output

monitoring item.

 

Output signal 0 to 5VDC

 

 

 

 

 

 

Permissible load current 1mA

 

 

 

 

 

 

 

 

 

 

Using the parameter unit connection cable (FR-CB201 to

−−RS-485 connector 205), the parameter unit (FR-PU04) is connectable.

(*3)Communication operation can be performed through

RS-485.

*1. Do not connect terminals SD and PC each other or to the earth.

For sink logic, terminal SD acts as the common terminal of contact input. For source logic, terminal PC acts as the common terminal of contact input. (Refer to page 25 for the way to switch between them.)

*2. Low indicates that the open collector outputting transistor is on (conducts). High indicates that the transistor is off (does not conduct).

*3. Compatible with only the type having RS-485 communication function. (Refer to page 41.)

*4. RL, RM, RH, RT, AU, STOP, MRS, OH, REX, JOG, RES, X14, X16, (STR) signal selection (Refer to page 88.)

*5. RUN, SU, OL, FU, RY, Y12, Y13, FDN, FUP, RL, LF, ABC signal selection (Refer to page 90.)

*6. To be compatible with the European Directive (Low Voltage Directive), the operating capacity of relay outputs (A, B, C) should be 30V 0.3A DC.