Mitsubishi FR - S500 Motor rotates in opposite direction, Speed greatly differs from the setting

Models: FR - S500

1 191
Download 191 pages 47.82 Kb
Page 156
Image 156

3.2.2 Motor rotates in opposite direction

Check that the phase sequence of output terminals U, V and W is correct. Check that the start signals (forward rotation, reverse rotation) are connected properly.

Check the setting of Pr. 17 "RUN key rotation direction selection".

3.2.3 Speed greatly differs from the setting

Check that the frequency setting signal is correct. (Measure the input signal level.)

Check that the following parameter settings are correct (Pr. 1, Pr. 2, Pr. 19, Pr. 38, Pr. 39, Pr. 95, C2 to C7).

Check that the input signal lines are not affected by external noise. (Use shielded cables)

Check that the load is not too heavy.

3.2.4 Acceleration/deceleration is not smooth

Check that the acceleration and deceleration time settings are not too short. Check that the load is not too heavy.

Check that the torque boost setting is not too large to activate the stall prevention function.

3.2.5 Motor current is large

Check that the load is not too heavy.

Check that the torque boost setting is not too large.

3.2.6 Speed does not increase

Check that the maximum frequency setting is correct.

Check that the load is not too heavy. (In agitators, etc., load may become heavier in winter.)

Check that the torque boost setting is not too large to activate the stall prevention function.

3.2.7 Speed varies during operation

When slip compensation is selected, the output frequency varies with load fluctuation between 0 and 2Hz. This is a normal operation and is not a fault.

1) Inspection of load

Check that the load is not varying.

2) Inspection of input signal

Check that the frequency setting signal is not varying.

Check that the frequency setting signal is not affected by noise.

Check for a malfunction due to an undesirable current when the transistor output unit is connected. (Refer to page 25)

3) Others

Check that the wiring is within specified length.

Check that the inverter is either FR-S540-1.5K, 2.2K or 3.7K and GD2 load is samll (at the mnitor GD2 or smaller)

If so, set the Pr. 72 "PWM frequency selection" to 6kHz or higher. When setting the PWM to a higher frequency, check for noise or leakage current problem and take countermeasures against it.

147