Operation Panel Indication

Er2

 

 

FR-PU04

In PU/EXT Mode

 

 

OPERATOR ERR

 

 

 

 

 

Name

Write-while-running error/mode designation error

 

Write was performed during operation.

 

Description

An attempt was

made to change the Pr. 79 setting to the

operation mode where the operation command has been input.

 

 

Write was performed in the external operation mode.

 

After stopping operation, make parameter setting.

Corrective action

After setting the operation mode to the "PU operation mode",

 

make parameter setting. (Refer to page 98)

Operation Panel Indication

Er3

 

FR-PU04

Incr I/P

 

 

 

 

 

Name

Calibration error

 

 

Description

Analog input bias and gain calibration values are too close.

Corrective action

Check the settings of C3, C4, C6 and C7 (calibration functions).

(Refer to page 74)

 

 

 

 

 

3

144

Page 153
Image 153
Mitsubishi FR - S500 instruction manual 144, Er2 FR-PU04 PU/EXT Mode, Operator ERR, Er3 FR-PU04 Incr I/P