Operation Panel Indication

OC2

 

 

FR-PU04

Stedy Spd OC

 

 

 

 

 

Name

Overcurrent cut-off during constant speed

 

When the inverter output current reaches or exceeds

Description

approximately 200% of the rated inverter current during constant-

speed operation, the protective circuit is activated to stop the

 

 

inverter output.

 

 

Check point

Check for sudden load change.

 

 

Check for output short-circuit/ground fault.

 

Corrective action

Keep load stable.

 

 

Operation Panel Indication

OC3

 

 

FR-PU04

OC During Dec

 

 

 

 

 

Name

Overcurrent cut-off during deceleration

 

When the inverter output current reaches or exceeds

Description

approximately 200% of the rated inverter current during

deceleration (other than acceleration or constant speed), the

 

 

protective circuit is activated to stop the inverter output.

 

Check for sudden speed reduction.

Check point

Check for output short-circuit/ground fault.

 

Check for too fast operation of motor's mechanical brake.

Corrective action

Increase the deceleration time.

 

 

Adjust brake operation.

 

 

 

 

 

Operation Panel Indication

OV1

 

FR-PU04

OV During Acc

 

 

 

 

 

Name

Regenerative overvoltage cut-off during acceleration

 

When the main circuit DC voltage in the inverter rises to or above

 

the specified value due to excessive regenerative energy during

Description

acceleration, the protective circuit is activated to stop the inverter

 

output. The circuit may also be activated by a surge voltage

 

produced in the power supply system.

Check point

Check for too slow acceleration.

Corrective action

Decrease the acceleration time.

Install a power factor improving reactor.

 

Operation Panel Indication

OV2

 

 

FR-PU04

Stedy Spd OV

 

 

 

 

 

Name

Regenerative overvoltage cut-off during constant speed

 

When the main circuit DC voltage in the inverter rises to or above

 

the specified value due to excessive regenerative energy during

Description

constant speed, the protective circuit is activated to stop the

 

inverter output. The circuit may also be activated by a surge

 

voltage produced in the power supply system.

Check point

Check for sudden load change.

 

 

Corrective action

Keep load stable.

 

 

Install a power factor improving reactor.

 

138

3

Page 147
Image 147
Mitsubishi FR - S500 instruction manual 138, OC2 FR-PU04, OC3 FR-PU04, OV1 FR-PU04, OV2 FR-PU04