Operation Panel Indication

GF

 

FR-PU04

Ground Fault

 

 

 

 

 

Name

Start-time output side ground fault overcurrent protection

 

This function stops the inverter output if a ground fault overcurrent

Description

flows due to a ground fault which occurred in the inverter's output

(load) side. Made valid when Pr. 40 "start-time ground fault

 

 

detection selection" = "1".

 

 

Check point

Check for a ground fault in the motor and connection cable.

Corrective action

Remedy the ground fault portion.

Operation Panel Indication

OHT

 

 

FR-PU04

OH Fault

 

 

 

 

 

 

Name

External thermal relay (*2)

 

 

 

If the external thermal relay designed for motor overheat

 

protection or the internally mounted temperature relay in the

Description

motor switches on (contacts open), the inverter output is stopped.

 

If the relay contacts are reset automatically, the inverter will not

 

restart unless it is reset.

 

 

 

Check for motor overheating.

 

 

Check point

Check that the value of 7 (OH signal) is set correctly in any of

 

Pr. 60 to Pr. 63 (input terminal function selection).

Corrective action

Reduce the load and operating duty.

*2. Functions only when any of Pr. 60 to Pr. 63 (input terminal function selection) is set to OH.

Operation Panel Indication

OLT

 

FR-PU04

Stll Prev STP

 

 

 

 

 

Name

Stall prevention (overload)

 

 

 

The running frequency has fallen to 0 by stall prevention

Description

operation activated. OL appears while stall prevention is being

 

activated.

 

 

Check point

Check the motor for use under overload.

Corrective action

Reduce the load weight.

 

 

Operation Panel Indication

OPT

 

FR-PU04

Option Fault

 

 

 

 

 

Name

Communication error (*3)

 

 

 

Stops the inverter output if a setting error or connection

Description

(connector) fault occurs during use of the RS-485 communication

 

function.

 

 

Check point

Check that the connector is plugged securely.

Corrective action

Make connection securely.

 

 

Please contact your sales representative.

 

Operation Panel Indication

PE

 

FR-PU04

Corrupt Memory

 

 

 

 

 

Name

Parameter error

 

 

Description

A fault occurred in parameters stored

(example: E2PROM fault).

 

 

 

 

 

Check point

Check for too many number of parameter write times.

Corrective action

Please contact your sales representative.