(1) PU operation interlock

PU operation interlock forces the operation mode to be changed to the external operation mode when the MRS signal switches off. This function prevents the inverter from being inoperative by the external command if the mode is accidentally left unswitched from the PU operation mode.

1) Preparation

Set "7" in Pr. 79 (operation mode selection).

Set the terminal used for MRS signal input with any of Pr. 60 to Pr. 63 (input terminal function selection).

Refer to page 88 for Pr. 60 to Pr. 63 (input terminal function selection).

REMARKS

When terminal assignment is changed using Pr. 60 to Pr. 63, the other functions may be affected.

Check the functions of the corresponding terminals before making settings.

2) Function

MRS Signal

Function/Operation

 

Output stopped during external operation.

ON

Operation mode can be switched to PU operation mode.

Parameter values can be rewritten in PU operation mode.

 

 

PU operation allowed.

 

Forcibly switched to external operation mode.

OFF

External operation allowed.

 

Switching to PU operation mode inhibited.

<Function/operation changed by switching on-off the MRS signal>

Operating Condition

MRS

Operation

 

Parameter

Switching to

Operation

Status

Mode

Operating Status

PU Operation

mode

Signal

(*2)

 

Write

Mode

 

 

 

 

 

 

During

ON

OFF

 

During stop

Allowed

Disallowed

 

stop

(*1)

 

disallowed

 

 

 

 

 

 

 

 

 

If external operation

 

 

PU

 

 

 

PU

frequency setting

 

 

During

ON

OFF

External

and start signal are

Allowed

 

 

Disallowed

 

operation

(*1)

 

entered, operation is

disallowed

 

 

 

 

 

 

 

 

performed in that

 

 

 

 

 

 

 

status.

 

 

 

 

OFF

ON

 

 

Disallowed

Allowed

 

During

 

 

disallowed

 

 

 

 

During stop

 

 

stop

ON

OFF

 

Disallowed

Disallowed

 

 

 

 

 

 

 

disallowed

External

 

 

 

External

 

 

 

OFF

ON

During operation

Disallowed

Disallowed

 

 

 

 

During

 

output stop

disallowed

 

 

 

 

 

 

operation

ON

OFF

 

Output stop

Disallowed

Disallowed

 

 

 

 

 

operation

disallowed

 