2.9.2 Output terminal function selection

You can change the functions of the open collector and contact output terminals.

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

 

RUN terminal

 

 

 

64

function

0

 

 

 

selection

 

 

 

 

 

 

0, 1, 3, 4,

 

 

 

 

11 to 16,

Setting is enabled when Pr. 30 = "1"

 

 

 

 

A, B, C

 

98, 99

 

 

 

 

 

65

terminal

99

 

 

function

 

 

 

 

 

 

 

selection

 

 

 

 

 

 

 

 

<Setting>

Setting

Signal

Function

Operation

Parameters

 

Name

 

 

Referred to

 

 

 

Output during operation when the

 

0

RUN

Inverter running

inverter output frequency rises to or

Pr. 2, Pr.13

 

 

 

above the starting frequency.

 

1

SU

Up to frequency

Output when the output frequency is

Pr. 41

reached.

 

 

 

 

3

OL

Overload alarm

Output while stall prevention function

Pr. 21, Pr. 22,

is activated.

Pr. 23, Pr. 28

 

 

 

4

FU

Output frequency

Output when the output frequency

Pr. 42, Pr. 43

detection

rises to or above the setting.

 

 

 

 

 

Inverter operation

Output when the inverter is ready to

 

11

RY

be started by switching the start

ready

 

 

signal on.

 

 

 

 

 

12

Y12

Output current

Output when the output current rises

Pr. 48, Pr. 49

detection

to or above the setting.

 

 

 

13

Y13

Zero current

Output when the output current

Pr. 50, Pr. 51

detection

reaches 0.

 

 

 

14

FDN

PID lower limit

 

 

15

FUP

PID upper limit

Outputs the detection signal under

Pr. 88 to Pr. 94

16

RL

PID forward-reverse

PID control.

 

rotation output

 

 

 

 

 

 

 

 

 

Output when a minor fault (fan failure

 

98

LF

Minor fault output

or communication error warning)

Pr. 76, Pr. n5

 

 

 

occurs.

 

 

 

 

Output when the inverter's protective

 

99

ABC

Alarm output

function is activated to stop the output

 

 

 

(major fault).

 

REMARKS

The same function may be set to more than one terminal.