Mitsubishi FR - S500 instruction manual Adjustment procedure, 106

Models: FR - S500

1 191
Download 191 pages 47.82 Kb
Page 115
Image 115

Parameter

Name

Setting

Description

Number

 

 

 

 

 

 

Time required for the integral (I) action to provide the

 

PID integral

0.1 to 999s

same manipulated variable as that for the proportional

90

(P) action. As the integral time decreases, the set point

 

time

 

is reached earlier but hunting occurs more easily.

 

 

 

 

 

- - -

No integral control.

 

 

 

Set the upper limit. If the feedback value exceeds the

91

PID upper

0 to 100%

setting, the FUP signal is output. (Process value of

limit

 

4mA is equivalent to 0% and 20mA to 100%.)

 

 

 

 

- - -

No function

 

 

 

Set the lower limit. (If the feedback value falls below

 

PID lower

0 to 100%

the setting, the FDN signal is output. In this case, the

92

process value of 4mA is equivalent to 0% and 20mA to

limit

 

 

 

100%.)

 

 

 

 

 

- - -

No function

 

 

 

Valid only when Pr. 79 = "3" (n9 = 0 for computer link

 

 

 

operation) under the PU command in the PU operation

 

PID action

 

or PU/external combined mode. (When the computer

 

 

has the speed command write in the computer link

93

set point for

0 to 100%

operation mode (NET))

 

PU operation

 

 

 

For external operation, the voltage across 2-5 is the

 

 

 

 

 

 

set point.

 

 

 

(C3 value is equivalent to 0% and C4 value to 100%.)

 

 

 

Time required for the differential (D) action to provide

 

PID

0.01 to 10s

the same process value as that for the proportional (P)

94

differential

 

action. As the differential time increases, greater

 

time

 

response is made to a deviation change.

-- - No differential control.

(6)Adjustment procedure

Parameter setting

Adjust the PID control parameters, Pr. 88 to Pr. 94.

 

 

 

 

 

Terminal setting

Set the I/O terminals for PID control.

 

 

(Use Pr. 64 and Pr. 65 (output terminal function selection) to set the

 

 

 

 

FUP and FDN signals.)

 

 

(Use any of Pr. 60 to Pr. 63 (input terminal function selection) to set

 

 

the X14 signal.)

 

 

 

Turn on X14 signal.

 

 

 

 

 

 

Run

 

106

Page 115
Image 115