1.2 North America Version

1.2.1 Terminal connection diagram

FR-S520-0.1K to 3.7K-NA

FR-S540-0.4K to 3.7K-NA (R)

Inverter

NFB MC

3-phase AC R

power supplyS T

External transistor common 24VDC power supply PC

Contact input common (source)

Take care not to short terminals PC-SD.

Forward rotation start STF

U

V

W

P1

P

N

Motor

IM

Earth

(Ground)

Power factor improving DC reactor (FR-BEL: Option)

Jumper: Remove this jumper when FR-BEL is connected.

Reverse rotation start

 

 

*4

 

 

*5

A

 

 

 

 

 

 

 

 

 

 

High

RH

*4

 

 

*5

B

 

Alarm

 

Multi-speed selection Middle

RM

*4

 

 

*5

C

 

output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

RL

*4

 

 

 

 

 

 

Running

Operation status

Contact input common

SD

 

 

 

 

 

 

 

output

 

 

 

 

SE

 

 

 

 

 

 

 

Open collector

Open

Control input signals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

output common

collector

(No voltage input allowed)

 

 

SINK

 

 

 

 

 

 

 

outputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(*2)

 

 

 

 

 

 

 

 

 

Frequency setting signals (Analog)

 

SOURCE

 

 

 

 

 

 

 

 

Frequency

 

3

2

 

 

10 (+5V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setting

 

 

 

 

 

 

DC 0 to 5V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

potentiometer

 

 

 

 

 

2 DC 0 to 10V Selected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

1/2W1k

 

 

 

 

5 (Common)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(*3)

Current input (-)

 

 

 

 

 

 

AM

 

 

 

(+) Analog signal

4 to 20mADC (+)

4 (4 to 20mADC)

 

 

 

 

 

 

 

 

 

 

 

output

When using the current input as

 

 

 

 

 

 

5

 

 

(-)

(0 to 5VDC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the frequency setting signal, set

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

"4" in any of Pr. 60 to Pr. 63 (input

 

RS-485 Connector (*1)

 

 

 

 

 

terminal function selection), assign

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AU (current input selection) to any

 

Earth (Ground)

of terminals RH, RM, RL and STR,

 

 

 

and turn on the AU signal.

 

 

Main circuit terminal Control circuit input terminal Control circuit output terminal

REMARKS

*1 Only the type with RS-485 communication function.

*2 You can switch between the sink and source logic positions. Refer to page 25.

*3 When the setting potentiometer is used frequently, use a 2W 1kpotentiometer. *4 The terminal functions change with input terminal function selection (Pr. 60 to

Pr. 63). (Refer to page 38, 88) (RES, RL, RM, RH, RT, AU, STOP, MRS, OH, REX, JOG, X14, X16, (STR) signal selection)

*5 The terminal functions change with output terminal function selection (Pr. 64, Pr. 65). (Refer to page 90) (RUN, SU, OL, FU, RY, Y12, Y13, FDN, FUP, RL, LF, ABC signal selection)