Mitsubishi FR - S500 Output shut-off MRS signal Setting, External thermal relay input Setting

Models: FR - S500

1 191
Download 191 pages 47.82 Kb
Page 48
Image 48

1.8.5 Output shut-off (MRS signal): Setting "6"

Short the output stop terminal MRS-SD during inverter output to cause the inverter to immediately stop the output. Open terminals MRS-SD to resume operation in about 10ms. Terminal MRS may be used as described below:

(1) To stop the motor by

frequency

Motor coasted

 

Terminals MRS-SD must be shorted

to stop

 

mechanical brake (e.g.

 

 

electromagnetic brake)

 

 

 

when the mechanical brake is

Output

0.5Hz

 

operated and be opened before motor

Pr. 13

restart.

 

 

"starting

(2) To provide interlock to disable

 

 

frequency"

operation by the inverter

Across

ON

 

After MRS-SD have been shorted, the

MRS -SD

 

 

 

inverter cannot be operated if the start

Across

ON

 

signal is given to the inverter.

STF-SD

 

 

(STR)

 

 

 

 

 

(3) To coast the motor to stop

The motor is decelerated according to the preset deceleration time and is stopped by operating the DC injection brake at 3Hz or less. By using terminal MRS, the motor is coasted to a stop.

1.8.6 External thermal relay input: Setting "7"

When the external thermal relay or thermal relay built in the motor is actuated, the inverter output is shut off and an alarm signal is given to keep the motor stopped to protect the motor from overheat. If the thermal relay contact is reset, the motor is not restarted unless the reset terminal RES-SD is shorted for more than 0.1s and then opened or power-on reset is performed.

The function may therefore be used as an external emergency stop signal input.

Thermal relay

Inverter

Motor

U

 

V

IM

W

1

OH

 

SD

 

39

Page 48
Image 48
Mitsubishi FR - S500 instruction manual Output shut-off MRS signal Setting, External thermal relay input Setting