2.5.2 Zero current detection

When the inverter's

Start signal

OFF

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.50

output current falls to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

"zero

"0", torque will not be

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

 

Pr.50

 

 

 

 

 

 

 

 

 

 

 

 

 

current

generated. This may

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100ms

 

detection

current 0 [A]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cause a gravity drop

Zero current

 

 

OFF

 

 

ON

 

 

OFF

ON

level"

when the inverter is

detection signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.51

 

Pr.51

 

used in vertical lift

output (Y13)

 

 

 

 

 

 

 

 

 

 

 

detection time

 

detection time

 

 

 

 

 

 

 

application.

To prevent this, the output current "zero" signal can be output from the inverter to close the mechanical brake when the output current has fallen to "zero".

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

50

Zero current detection

5%

0 to 200%

 

level

Setting is enabled when Pr. 30

51

Zero current detection

0.5s

0.05 to 1s

= "1"

 

time

 

 

 

POINT

If the output is lower than the Pr.50 setting for longer than the time set in Pr. 51 during inverter operation, the zero current detection (Y13) signal is output from the inverter's open collector output terminal.

<Setting>

Parameter

Description

 

Set the zero current detection level.

50Set the level of zero current detection in terms of the percentage of the rated inverter current from the output current value of 0 [A].

Set the zero current detection time.

51Set a period of time from when the output current falls to or below the Pr. 50 setting to when the zero current detection signal (Y13) is output.

CAUTION

If the current falls below the preset detection level but the timing condition is not

satisfied, the zero current detection signal is held on for about 100ms.

2

When the terminal functions are changed using Pr. 64, Pr. 65, the other functions

 

 

may be affected. Confirm the functions of the corresponding terminals before

 

making settings.

 

When one inverter is used to run (connect) multiple motors sequentially, the zero

 

 

current detection signal (Y13) may be output. Set 13% or more for the 0.1K, and

 

 

8% or more for the 0.2K. (If the sum of motor capacities is less than the zero

 

current detection level current or if the motor capacity per motor is less than the zero current detection level current)

Related parameters

Assignment of Y13 signal to terminal Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C terminal function selection" (refer to page90)

81

Page 90
Image 90
Mitsubishi FR - S500 instruction manual Zero current detection