Checking the inverter and converter modules <Preparation>

(1)Disconnect the external power supply cables (R, S, T) and motor cables (U, V, W).

(2)Prepare a meter. (Use 100range.)

<Checking method>

Change the polarity of the meter alternately at the inverter terminals R, S, T, U, V, W, P and N, and check for continuity.

CAUTION

Before measurement, check that the smoothing capacitor is discharged.

At the time of continuity, the measured value is several to several ten's-of ohms depending on the number of modules, number of parallel modules, circuit tester type, etc. If all measured values are almost the same, the modules are without fault.

<Module device numbers and terminals to be checked>

 

 

Tester Polarity

 

Measured

 

 

Tester Polarity

Measured

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value

 

 

 

 

Value

Converter module

D1

R

P

 

Discontinuity

D4

R

N

Continuity

P

R

 

Continuity

 

N

R

Discontinuity

 

 

 

 

D2

S

P

 

Discontinuity

D5

S

N

Continuity

P

S

 

Continuity

 

N

S

Discontinuity

 

 

 

 

D3

T

P

 

Discontinuity

D6

T

N

Continuity

 

P

T

 

Continuity

 

N

T

Discontinuity

 

 

 

 

 

 

TR1

U

P

 

Discontinuity

TR4

U

N

Continuity

Inverter module

P

U

 

Continuity

 

N

U

Discontinuity

 

 

 

 

TR3

V

P

 

Discontinuity

TR6

V

N

Continuity

P

V

 

Continuity

 

N

V

Discontinuity

 

 

 

 

TR5

W

P

 

Discontinuity

TR2

W

N

Continuity

 

 

 

P

W

 

Continuity

 

N

W

Discontinuity

 

 

 

 

 

 

 

 

 

 

 

 

 

(Assumes the use of an analog meter.)

 

 

Converter

P

 

 

 

 

 

 

 

module

 

Inverter module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TR1

TR3

TR5

 

 

 

 

D1

D2

D3

 

 

 

 

 

 

 

 

R

 

 

 

C

 

 

 

U

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

 

 

 

 

 

 

 

V

 

 

 

T

 

 

 

 

 

 

 

W

 

 

 

D4

D5

D6

 

 

 

 

 

 

 

 

 

 

 

 

 

TR4

TR6

TR2

 

 

 

 

 

 

 

 

N

 

 

 

 

 

REMARKS

 

 

 

 

 

 

 

 

 

 

The FR-S520S-0.1K to 1.5K and FR-S510W-0.1K to 0.75K do not have T, D3 and D6.

153

Page 162
Image 162