Item

Measuring Point

Frequency setting

Across 10 (+)-5

power supply

 

 

 

 

Across FM (+)-SD

Frequency meter

 

signal

 

 

 

 

Across AM (+)-5

 

 

Start signal

Across STF, STR,

RH, RM, RL, MRS,

Select signal

RES-SD

 

Alarm signal

Across A-C

Across B-C

 

 

 

Measuring

 

 

 

 

 

Remarks

 

 

Instrument

 

(Reference Measured Value)

 

5VDC

 

 

"5"is

common.

 

 

 

 

 

 

 

 

 

 

Approximately 5VDC at

 

 

 

maximum frequency

 

 

 

 

 

(without frequency meter)

 

 

Moving-coil type

 

 

 

 

 

T1

 

 

is common.

(Meter, etc. may be

 

 

 

 

 

 

 

 

 

 

 

 

 

8VDC

 

 

 

 

 

 

used)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Internal resistance:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T2

 

 

 

 

50kor larger)

 

 

 

 

 

 

 

 

 

SD

Pulse width T1:

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjusted with C1

 

 

 

 

 

Pulse cycle T2:

 

 

 

 

 

 

 

Set with Pr. 55 (Pr,56)

 

 

 

Approximately 5VDC at

is5

common.

 

 

 

 

maximum frequency

 

 

 

 

 

(without frequency meter)

 

 

Moving-coil type

 

 

 

 

 

 

 

 

 

 

 

isSD

common.

(Meter, etc. may be

20 to 30VDC when open.

 

 

used)

ON voltage: 1V or less

 

 

(Internal resistance:

SD is common.

 

 

 

 

50kor larger)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Continuity check

 

 

 

 

 

 

 

 

 

<Normal>

<Fault>

Moving-coil type

Across Discontinuity

Continuity

(such as a meter)

A-C:

 

 

 

 

 

Across Continuity

Discontinuity

 

B-C:

 

 

 

 

CAUTION

1.Use FFT to measure the output voltage accurately. It can not be measured accurately with a meter or general instrumentation.

2.When the carrier frequency exceeds 5kHz, do not use the instrument because overcurrent losses occurring in the metallic parts inside the instrument will increase and may lead to burnout.

In this case, use an approximate effective value type instrument.

159