Mitsubishi FR - S500 Restart Operation Parameters, Monitoring reference, Restart setting

Models: FR - S500

1 191
Download 191 pages 47.82 Kb
Page 93
Image 93
The Japanese version has the FM terminal feature, and the NA and EC versions have the AM terminal feature.

2.6.3 Monitoring reference

Set the frequency or current which is referenced when the output frequency or output current is selected for the FM (AM) terminal.

1440 pulses/s (terminal FM)

(5VDC (terminal AM))

Outputor display

 

Output

Pr.55

frequency

 

1440 pulses/s (terminal FM)

(5VDC (terminal AM))

Outputor display

 

Output

Pr.56

frequency

 

Parameter

Name

Factory

Setting

<EC version>

Setting Range

Remarks

55

Frequency monitoring

60Hz

0 to 120Hz

reference

<50Hz>

 

 

56

Current monitoring

Rated output

0 to 50A

reference

current

 

 

Setting is enabled when Pr. 30 = "1"

<Setting>

Refer to the above diagrams and set the frequency monitoring reference value in Pr. 55 and the current monitoring reference value in Pr. 56.

Pr. 55 is set when Pr. 54 "FM (AM) terminal function selection" = "0" and Pr. 56 is set when Pr. 54 = "1".

Set the Pr. 55 and Pr. 56 values so that the output pulse train output of terminal FM is 1440 pulses/s (the output voltage of terminal AM is 5V).

CAUTION

The maximum pulse train output of terminal FM is 2400pulses/s. If Pr. 55 is not adjusted, the output of terminal FM will be filled to capacity. Therefore, adjust Pr. 55.

The maximum output voltage of terminal AM is 5VDC.

2.7 Restart Operation Parameters

2.7.1 Restart setting

At power restoration after an instantaneous power failure, you can restart the inverter without stopping the motor (with the motor coasting).

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

57

Restart

- - -

0 to 5s,

 

coasting time

- - -

 

 

 

Setting is enabled when Pr. 30 = "1"

58

Restart cushion

1s

0 to 60s

 

time

 

 

 

 

 

84

Page 93
Image 93
Mitsubishi FR - S500 instruction manual Restart Operation Parameters, Monitoring reference, Restart setting