2.3 Explanation of Functions (Parameters)

2.3.1 Torque boost

Increase this value for use when the inverter-to-motor distance is long or motor torque is insufficient in the low speed range (stall prevention is activated).

Motor torque in the low-frequency range can be adjusted to the load to increase the starting motor torque.

 

Output voltage

Pr.0

Setting range

Pr.46

 

0 Output frequency (Hz)

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

 

 

 

 

(Note) FR-S520 (S)-0.1K to 3.7K: 6%

 

 

6%/5%/4%

 

FR-S540-0.4K, 0.75K: 6%

0

Torque boost

0 to 15%

FR-S510W-0.1K to 0.75K: 6%

 

 

(Note)

 

FR-S540-1.5K, 2.2K: 5%

 

 

 

 

 

 

 

 

FR-S540-3.7K: 4%

46

Second torque boost

- - -

0 to 15%,

- - -: Function invalid. Setting is

- - -

enabled when Pr. 30 = "1".

 

 

 

<Setting>

Assuming that the base frequency voltage is 100%, set the 0Hz voltage in %.

Use the RT signal to switch between two different torque boosts. (Turn on the RT signal to make Pr. 46 valid(*).)

REMARKS

*The RT signal acts as the second function selection signal and makes the other second functions valid.

When using an inverter-dedicated motor (constant-torque motor), make setting as indicated below.

FR-S520-0.1K to 0.75K ..... 6%, FR-S520-1.5K to 3.7K ..... 4%

FR-S540-0.4K, 0.75K ..... 6%, FR-S540-1.5K ..... 4%, FR-S540-2.2K, 3.7K ..... 3%

FR-S520S-0.1K to 0.75K ..... 6%, FR-S520S-1.5K ..... 4%

FR-S510W-0.1K to 0.75K ..... 6%

If you leave the factory setting as it is and change the Pr. 71 value to the setting for use of the constant-torque motor, the Pr. 0 setting changes to the above value.

CAUTION

Selecting automatic torque boost control makes this parameter setting invalid.

A too large setting may cause the motor to overheat or result in an overcurrent trip. The guideline is about 10% at the greatest.

Related parameters

RT signal (second function "Pr. 46") settingPr. 60 to Pr. 63 "input terminal function selection" (refer to page 88)

Constant-torque motor setting Pr. 71 "applied motor" (refer to page 93)

Automatic torque boost control selection Pr. 98 "automatic torque boost selection (motor capacity)" (refer to page 109)