Changing example Deflecting the meter (analog indicator) to full-scale (5V) at the preset frequency of 60Hz (for frequency setting, refer to the instruction manual (basic).)

POINT

The calibration parameters "C1" can be made to be ready by setting "1" (extended function parameter valid) in Pr. 30 "extended function display selection".

Set the value of the calibration parameter C1 "AM terminal calibration".

Operation

1. Confirm the RUN indication and operation mode indication.

The inverter must be at a stop.

2.

Press the MODE key to choose the

 

parameter setting mode.

MODE

 

 

3. Turn the setting dial

to show

 

"

" .

 

 

 

Pr. 30 must be set to "1".

(For details, refer to the instruction manual (basic)).

Display

RUN

PU

EXT

The parameter number read previously appears.

4. Press the

SET

key to show

 

SET

 

 

 

 

 

"

" .

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5. Turn the setting dial

until the

 

 

 

 

 

 

calibration parameter C1 "AM

 

 

 

 

 

 

terminal calibration" appears.

 

 

 

 

 

 

6. Press the

SET

key to enable setting.

SET

 

 

 

 

 

7. Press the

RUN

key to start the

 

 

 

 

 

RUN

RUN

 

 

 

 

PU

inverter. (The motor need not be

 

 

 

 

 

EXT

connected.)

 

 

 

+

 

 

 

 

 

8. Turn the setting dial

to

 

 

Analog indicator

 

 

 

adjust the indicator needle

 

 

 

 

 

 

 

 

 

 

to the desired position.

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

9. Press the

SET

key.

 

 

SET

 

 

 

 

 

Setting is complete.

 

Flicker ... Parameter setting complete!!

 

 

 

 

 

 

 

By turning the setting dial

, you can read another parameter.

 

 

Press the

SET

key to return to the

indication (step 4).

 

 

Press the

SET

key twice to show the next parameter (

).

REMARKS

Depending on the set value, it may take some for the needle to move.

If "1" is set in Pr. 30 "extended function display selection", the calibration parameter C1 "AM terminal calibration" can also be set in the external operation mode.

When the FR-PU04 is used, make calibration with Pr. 901.

114