3.3.8 Measurement of main circuit voltages, currents and powers

Measurement of voltages and currents

Since the voltages and currents on the inverter power supply and output sides include harmonics, accurate measurement depends on the instruments used and circuits measured.

When instruments for commercial frequency are used for measurement, measure the following circuits using the instruments given on the next page.

Three-phase 200V power input Three-phase 400V power input

Input

Output

voltage

voltage

Input

Output

current

current

Single-phase 200V

power input

Single-phase 100V

power input

Inverter

 

Ar

W11

3-phase

 

Vr

As

W12

power supply

 

Vs

 

 

 

At

W13

 

 

Vt

The FR-S520S-0.1K to 1.5K and FR-S510W-0.1K to 0.75K do not have As, At, Vt, Vs, W12 and W13.

Instrument types

R

U

Au

W21

 

 

 

Vu

S

V

Av

 

 

 

 

Vv

T

W

Aw

W22

 

 

 

Vw

P

N

 

 

 

V

 

 

+

-

 

 

To motor

:Moving-iron type

:Electrodynamometer type

:Moving-coil type

:Rectifier type

Typical Measuring Points and Instruments

CAUTION

Use FFT (Fast Fourier Transforms) to measure the output voltage accurately. It cannot be measured accurately with a meter or general instrument.