2.14.2 Operation and speed command write

Used to make valid the operation and speed commands from the computer or external terminals.

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

n8 (338)

Operation

0

0, 1

 

command write

Setting is enabled when Pr. 30 = "1"

n9 (339)

Speed command

0

0, 1

 

write

 

The parameter numbers within parentheses are those for use of the parameter unit (FR-PU04).

<Setting>

In the computer operation mode, commands from the external terminals and sequence program are as listed below.

(Refer to page 88 for Pr. 60 to Pr. 63 (input terminal function selection).)

Operation

location

selection

n8 (Pr. 338)

"operation

0:

0:

1:

1:

command write"

Computer

Computer

External

External

n9 (Pr. 339)

"speed

0:

1:

0:

1:

command write"

Computer

External

Computer

External

Remarks

 

Fixed

 

Forward rotation command

Computer

Computer

External

External

 

 

 

(STF)

 

 

function

 

 

 

 

 

 

Computer link operation

Computer

Computer

 

 

(Terminal-

 

 

frequency

 

 

equivalent

 

 

 

 

 

 

 

 

2

External

External

 

 

function)

 

 

 

 

4

External

External

 

 

 

 

 

 

 

 

 

0

Low-speed operation

Computer

External

Computer

External

Pr. 59 = "0"

 

 

 

command (RL)

 

 

 

1

Middle-speed operation

Computer

External

Computer

External

Pr. 59 = "0"

 

 

 

command (RM)

 

 

 

2

High-speed operation

Computer

External

Computer

External

Pr. 59 = "0"

 

 

 

command (RH)

 

 

 

3

Second function

Computer

Computer

External

External

 

 

 

 

selection (RT)

 

 

 

settings63

4

Current input selection

Either

Either

 

 

function

(AU)

 

 

 

 

5

Start self-holding

External

External

 

 

 

 

selection (STOP)

 

 

Selection

Pr.to60Pr.

6

Output stop (MRS)

Either

Either

External

External

Pr. 79 "7"

 

 

 

7

External thermal relay

External

External

External

External

 

 

 

 

input (OH)

 

 

 

 

8

15-speed selection

Computer

External

Computer

External

Pr. 59 = "0"

 

 

 

(REX)

 

 

 

9

Jog operation selection

External

External

 

 

 

 

(JOG)

 

 

 

 

10

Reset (RES)

Either

Either

Either

Either

 

 

 

 

14

PID control valid

Computer

External

Computer

External

 

 

 

 

terminal (X14)

 

 

 

 

16

PU-external operation

External

External

External

External

 

 

 

 

switch-over (X16)

 

 

 

 

- - -

Reverse rotation

Computer

Computer

External

External

 

 

 

 

command (STR)

 

130

Page 139
Image 139
Mitsubishi FR - S500 instruction manual Operation and speed command write, Location Selection N8 Pr Operation Command write