Mitsubishi FR - S500 instruction manual Flicker ... Parameter setting complete, 112

Models: FR - S500

1 191
Download 191 pages 47.82 Kb
Page 121
Image 121

Changing example Deflecting the meter (analog indicator) to full-scale (1mA) at the preset frequency of 60Hz (for frequency setting, refer to the instruction manual (basic).)

POINT

The calibration parameters "C1" can be made to be ready by setting "1" (extended function parameter valid) in Pr. 30 "extended function display selection".

Set the value of the calibration parameter C1 "FM terminal calibration".

OperationDisplay

In PU operation mode

1. Press the MODE key to choose the

 

parameter setting mode.

2. Turn the setting dial

to show

 

"

" .

 

 

 

Pr. 30 must be set to "1".

 

 

(For details, refer to the instruction

 

 

manual (basic).)

 

3.

Press the SET key to show

 

"

" .

 

4. Turn the setting dial

until the

 

calibration parameter C1 "FM

terminal calibration" appears.

5. Press the SET key to enable setting.

6. If the inverter is at a stop, press the RUN key to start it. (The motor

need not be connected.)

MODE

SET

SET

RUN

The parameter number read previously appears.

RUN

PU

EXT

7.

8.

Turn the setting dial to adjust the indicator needle to the desired position.

Press the SET key.

Setting is complete.

+

Analog indicator

-

SET

Flicker ... Parameter setting complete!!

By turning the setting dial , you can read another parameter.

Press the SET key to return to the

indication (step 3).

Press the SET key twice to show the next parameter (

).

112