2)"Harmonic suppression guideline for specific consumers"

This guideline sets forth the maximum values of harmonic currents outgoing from a high-voltage or specially high-voltage consumer who will install, add or renew harmonic generating equipment. If any of the maximum values is exceeded, this guideline requires that consumer to take certain suppression measures.

Table 1 Maximum Values of Outgoing Harmonic Currents per 1kW Contract Power

Received Power Voltage

5th

7th

11th

13th

17th

19th

23rd

Over

23rd

 

 

 

 

 

 

 

 

6.6kV

3.5

2.5

1.6

1.3

1.0

0.9

0.76

0.70

22 kV

1.8

1.3

0.82

0.69

0.53

0.47

0.39

0.36

33 kV

1.2

0.86

0.55

0.46

0.35

0.32

0.26

0.24

(1)Application of the harmonic suppression guideline for specific consumers

New installation/addition/ renewal of equipment

Calculation of equivalent capacity sum

Not more than

 

 

 

 

 

 

 

reference capacity

Sum of equivalent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

capacities

 

 

 

 

 

 

 

 

 

 

 

 

 

Over reference

 

 

 

 

 

 

 

capacity

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

Calculation of outgoing

 

 

 

 

 

 

 

 

 

 

harmonic current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is outgoing harmonic

Over maximum value

 

 

 

current equal to or lower

 

 

 

 

 

 

 

 

 

 

 

 

than maximum value?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Harmonic suppression

 

 

Not more than

technique is required.

 

 

 

 

 

maximum value

 

 

 

 

 

 

 

Harmonic suppression

 

 

 

 

 

 

technique is not required.

 

 

 

 

 

 

 