2.11.3 Motor primary resistance

Generally this parameter need not be set. At the factory setting of "- - -", the standard motor constant of the motor capacity set in Pr. 98 (including that of the constant-torque motor) is used.

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

99

Motor primary

- - -

0 to 50,

Setting is enabled when Pr. 30 = "1"

 

resistance

 

- - -

 

Related parameters

Applied motor setting Pr. 71 "applied motor" (refer to page 93)

Automatic torque boost selection Pr. 98 "automatic torque boost selection (motor capacity)"

(refer to page 109)

2.12 Calibration Parameters

2.12.1 Meter (frequency meter) calibration

(Japanese version)

By using the control panel or parameter unit, you can calibrate a analog meter connected to terminal FM to full scale deflection.

Terminal FM provides the pulse output. By setting the calibration parameter C1, you can use the parameter to calibrate the analog meter connected to the inverter without providing a calibration resistor.

Parameter

Name

Factory Setting

Setting Range

Remarks

C1 (900)

FM terminal

———

———

Setting is enabled when

calibration

Pr. 30 = "1"

 

 

 