2.3.2 Maximum and minimum frequency

You can clamp the upper and lower limits of the output frequency.

Output frequency (Hz)

 

Pr.1

 

Pr.2

Set frequency

 

0

5,10V

(4mA)

(20mA)

Parameter

Name

Factory Setting

Setting Range

<EC version>

 

 

 

1

Maximum frequency

60Hz <50Hz>

0 to 120Hz

2

Minimum frequency

0Hz

0 to 120Hz

<Setting>

Use Pr. 1 to set the upper limit of the output frequency. If the frequency of the frequency command entered is higher than the setting, the output frequency is clamped at the maximum frequency.

Use Pr. 2 to set the lower limit of the output frequency.

REMARKS

When using the potentiometer (frequency setting potentiometer) connected across terminals 2-5 to perform operation above 60Hz <50Hz>, change the Pr. 1 and Pr. 38 (Pr. 39 when using the potentiometer across terminals 4-5) values.

CAUTION

When the Pr. 2 setting is higher than the Pr. 13 "starting frequency" value, note that the motor will run at the set frequency by merely switching the start signal on, without entering the command frequency.

Related parameters

Starting frequency setting Pr. 13 "starting frequency" (refer to page 65) Maximum frequency setting using external potentiometer

Pr. 30 "extended function display selection" (refer to page 72), Pr. 38 "frequency setting voltage gain frequency", Pr. 39 "frequency setting current gain frequency" (refer to page 74)

2.3.3 Base frequency, Base frequency voltage

2

Used to adjust the inverter outputs (voltage, frequency) to the motor rating.

voltage

Pr.19

Output

Output

frequency (Hz)

Pr.3

 

 

Pr.47

59