Operation Panel Indication

OV3

 

FR-PU04

OV During Dec

 

 

 

 

 

Name

Regenerative overvoltage cut-off during deceleration or stop

 

When the main circuit DC voltage in the inverter rises to or above

 

the specified value due to excessive regenerative energy during

Description

deceleration or stop, the protective circuit is activated to stop the

 

inverter output. The circuit may also be activated by a surge

 

voltage produced in the power supply system.

Check point

Check for sudden speed reduction.

 

Increase the deceleration time. (Set the deceleration time which

Corrective action

matches the inertia moment of the load)

Decrease the braking duty.

 

 

 

 

 

 

Install a power factor improving reactor.

Operation Panel Indication

THM

 

 

FR-PU04

Motor Overload

 

 

 

 

 

Name

Motor overload cut-off (electronic thermal overcurrent protection)

(* 1)

 

 

 

 

 

 

 

 

 

 

The electronic overcurrent protection in the inverter detects motor

 

overheat due to overload or reduced cooling capability during low-

Description

speed operation to stop the inverter output. When a multi-pole

motor or two or more motors are run, provide a thermal relay in

 

 

the output side of the inverter.

 

 

 

Protection from burning due to motor temperature rise

Check point

Check the motor for use under overload.

 

Reduce the load weight.

 

 

Corrective action

For the constant-torque motor, change the Pr. 71 setting to the

 

constant-torque motor setting.

 

 

Operation Panel Indication

THT

 

FR-PU04

Inv. Overload

 

 

 

 

 

Name

Inverter overload cut-off (electronic thermal overcurrent protection)

(* 1)

 

 

 

 

 

 

 

 

If a current of more than 150% of the rated output current flows

 

and overcurrent shut-off does not occur (200% or less), inverse-

Description

time characteristics cause the electronic overcurrent protection to

be activated to stop the inverter output in order to protect the

 

 

output transistors.

 

 

 

Output transistor protection from overheat

Check point

Check the motor for use under overload.

Corrective action

Reduce the load weight.

 

 

*1. Resetting the inverter initializes the internal heat integrating data of the electronic overcurrent protection.

Operation Panel Indication

FIN

 

 

FR-PU04

H/Sink O/Temp

 

 

 

 

 

 

Name

Fin overheat

 

 

Description

If the cooling fin overheats, the overheat sensor is actuated to

stop the inverter output.

 

 

 

 

 

Check point

Check for too high ambient temperature.

Check for cooling fin clogging.

 

 

 

 

 

Corrective action

Set the ambient temperature to within the specifications.