<Setting>

Refer to the following table and set the parameters:

 

Setting

Signal

Functions

Related Parameters

 

Name

 

 

 

 

 

 

 

 

 

Pr. 59 = "0"

Low-speed operation

Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,

 

 

 

 

command

Pr. 80 to Pr. 87

 

0

RL

 

 

 

Pr. 59 = "1", "2" (*1)

 

Remote setting

Pr. 59

 

 

 

 

 

 

 

 

(setting clear)

 

 

 

 

 

 

 

 

 

Pr. 59 = "0"

 

Middle-speed

Pr. 4 to Pr. 6, Pr.24 to Pr. 27,

 

 

 

operation command

Pr.80 to Pr. 87

1

RM

 

Pr. 59 = "1", "2" (*1)

 

Remote setting

Pr. 59

 

 

 

 

 

 

 

 

(deceleration)

 

 

 

 

 

 

 

 

 

Pr. 59 = "0"

High-speed operation

Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,

 

 

 

 

command

Pr. 80 to Pr. 87

2

RH

 

 

Pr. 59 = "1", "2" (*1)

 

Remote setting

Pr. 59

 

 

 

 

 

 

 

 

(acceleration)

 

 

 

 

 

 

3

RT

Second function selection

Pr. 44 to Pr. 47

4

AU

Current input selection

 



5

STOP

Start self-holding selection



6

MRS

Output shut-off stop

 



 

 

 

External thermal relay input (*2)

 

 

 

 

The inverter stops when the externally

 

7

OH

provided overheat protection thermal

Refer to page 140.

 

 

 

relay, motor's embedded temperature

 

 

 

 

relay etc. is actuated.

 

 

8

REX

15-speed selection (combination with 3

Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,

speeds RL, RM, RH) (*3)

Pr. 80 to Pr. 87

 

 

 

9

JOG

Jog operation selection

Pr. 15, Pr. 16

10

RES

Reset

 

 

Pr. 75

14

X14

PID control presence/absence selection

Pr. 88 to Pr. 94

16

X16

PU-external operation switch-over

Pr. 79 (setting: 8)

- - -

STR

Reverse rotation start

 

(can be assigned to STR

 

terminal (Pr. 63) only)

 

 

 

 

 

 

*1 When Pr. 59 = "1 or 2", the functions of the RL, RM and RH signals change as listed above.

*2 Actuated when the relay contact "opens".

*3 When using the REX signal, an external command cannot be used to make a 2 reverse rotation start.

REMARKS

One function can be assigned to two or more terminals. In this case, the function is activated when one of the multiple terminals used for assignment turns on.

The speed command priorities are higher in order of jog, multi-speed setting (RH, RM, RL, REX) and AU.

Use common terminals to assign multi-speeds (7 speeds) and remote setting. They cannot be set individually.

(Common terminals are used since these functions are designed for speed setting and need not be set at the same time.)

89

Page 98
Image 98
Mitsubishi FR - S500 instruction manual Setting Signal Functions Related Parameters Name, Mrs, Rex, Jog, Res