(4)Single-phase 100V power supply

Japanese version

FR-S510W-0.1K to 0.75K (-R)

NA version

FR-S510W-0.1K to 0.75K-NA

Type FR-S510W-K(-R)

Applicable motor capacity

kW

(*1)

 

HP

 

 

 

Output

Rated capacity (kVA) (*2)

Rated current (A)

 

 

Overload capacity (*3)

 

Voltage

 

Rated input AC (DC) voltage,

supply

frequency

fluctuation

Power

Permissible AC (DC) voltage

Permissible frequency

 

 

fluctuation

 

Power supply system

 

capacity (kVA) (*5)

Protective structure (JEM1030)

Cooling system

Approximate weight (kg (lbs))

0.1

0.2

0.4

0.75

0.1

0.2

0.4

0.75

1/8

1/4

1/2

1

0.3

0.5

1.0

1.6

0.8

1.4

2.5

4.1

150% 60s 200% 0.5s (Inverse time characteristics)

Three phase, 200V to 230V 50Hz/60Hz (*4, 6)

Single-phase, 100V to 115V 50Hz/60Hz

90 to 132V 50Hz/60Hz

± 5%

0.5

0.9

1.5

2.5

 

 

 

 

 

Enclosed type (IP20)

 

 

Self-cooling

 

0.6

0.7

0.9

1.6

(1.32)

(1.54)

(1.98)

(3.52)

 

 

 

 

*1. The applicable motor capacity indicated is the maximum capacity applicable when a Mitsubishi 4-pole standard motor is used.

*2. The rated output capacity indicated assumes that the output voltage is 230V.

*3. The % value of the overload capacity indicates the ratio of the overload current to the inverter's rated output current.

For repeated duty, allow time for the inverter to return to or below the temperatures under 100% load.

*4. For single-phase 100V power input, the output voltage provided cannot be twice or more than the power supply voltage.

*5. The power supply capacity changes with the values of the power supply side inverter impedances (including those of the input reactor and cables).

*6. For single-phase 100V power input, the application of motor load reduces the output voltage about 10 to 15%. Therefore, the load must be reduced when a general-purpose motor is used.

4

164

Page 173
Image 173
Mitsubishi FR - S500 instruction manual Single-phase 100V power supply