Operation Panel Indication

PUE

 

FR-PU04

PU Leave Out

 

 

 

 

 

Name

PU disconnected (*3)

 

 

 

Stops the inverter output if communication between inverter and

Description

PU is suspended, e.g. if the PU is disconnected with "1" set in the

communication parameter n17 "PU disconnection detection/PU

 

 

setting lock".

 

 

 

Check that the FR-PU04 is fitted securely.

Check point

Check the setting of the communication parameter n17 "PU

 

disconnection detection".

 

 

Corrective action

Fit the FR-PU04 securely.

 

 

*3. For only the type having the RS-485 communication function.

Operation Panel Indication

RET

 

FR-PU04

Retry No Over

 

 

 

 

 

Name

Retry count

 

 

 

Description

If operation cannot be resumed properly within the number of

retries set, this function stops the inverter output.

 

Check point

Find the cause of alarm occurrence.

Corrective action

Eliminate the cause of the error preceding this error indication.

Operation Panel Indication

CPU

 

FR-PU04

CPU Fault

 

 

 

 

 

Name

CPU error

 

 

 

If the arithmetic operation of the built-in CPU does not end within

Description

a predetermined period, the inverter self-determines it as an

 

alarm and stops the output.

 

 

Check point

 

 



Corrective action

Please contact your sales representative.

(2) Minor failures

When the protective function is activated, the output is not shut off. You can make parameter setting to output the light fault signal. (Set "98" in any of Pr. 64, Pr. 65 (output terminal function selection). Refer to page 90)

Operation Panel Indication

FN

 

FR-PU04

 

FN

 

 

 

 

 

 

Name

Fan trouble

 

 

 

 

For the inverter which contains a cooling fan,

appears on the

Description

operation panel when the cooling fan stops due to a fault or

operates differently from the setting of Pr. 76 "cooling fan

 

 

operation selection".

 

 

 

Check point

Check the cooling fan for a fault.

 

Corrective action

Change the fan.

 

 

 

141

Page 150
Image 150
Mitsubishi FR - S500 Minor failures, For only the type having the RS-485 communication function, 141, Pue, Ret