Mitsubishi FR - S500 instruction manual 142

Models: FR - S500

1 191
Download 191 pages 47.82 Kb
Page 151
Image 151

(3) Warnings

Operation Panel Indication

OL

 

 

 

FR-PU04

OL

 

 

 

 

 

 

Name

Stall prevention (overcurrent)

 

 

 

 

 

If a current of more than 150% (* 4) of the rated

 

 

 

inverter current flows in the motor, this function

 

During

 

stops the increase in frequency until the overload

 

 

current reduces to prevent the inverter from

 

acceleration

 

 

 

resulting

in

overcurrent

shut-off. When the

 

 

 

 

 

 

overload current has reduced below 150%, this

 

 

 

function increases the frequency again.

 

 

 

If a current of more than 150% (* 4) of the rated

 

During

 

inverter current flows in the motor, this function

 

 

lowers the frequency until the overload current

 

constant-

 

Description

 

reduces to prevent overcurrent shut-off. When the

speed

 

 

 

overload current has reduced below 150%, this

 

operation

 

 

 

function increases the frequency up to the set

 

 

 

 

 

 

value.

 

 

 

 

 

 

If a current of more than 150% (* 4) of the rated

 

 

 

inverter current flows in the motor, this function

 

During

 

stops the decrease in frequency until the overload

 

 

current reduces to prevent the inverter from

 

deceleration

 

 

 

resulting

in

overcurrent

shut-off. When the

 

 

 

 

 

 

overload current has reduced below 150%, this

 

 

 

function decreases the frequency again.

Check point

Check the motor for use under overload.

 

 

The acceleration/deceleration time may change.

 

Increase the stall prevention operation level with Pr. 22 "stall

Corrective action

prevention operation

level", or disable

stall prevention with

Pr. 21 "stall prevention function selection".

 

 

 

 

Check that the torque boost (Pr. 0) setting is not higher than

 

required.

 

 

 

 

 

*4. The stall prevention operation current can be set as desired. It is factory-set to 150%.

Operation Panel Indication

oL

 

 

 

FR-PU04

oL

 

 

 

 

 

 

 

Name

Stall prevention (overvoltage)

 

 

 

 

 

If the regenerative energy of the motor increases

 

During

 

too much to exceed the brake capability, this

Description

 

function stops the decrease in frequency to prevent

deceleration

 

 

 

overvoltage shut-off. As soon as the regenerative

 

 

 

 

 

 

energy has reduced, deceleration resumes.

Check point

Check for sudden speed reduction.

Corrective action

The deceleration time may

change. Increase the deceleration

time using Pr. 8 "deceleration time".

 

3

142

Page 151
Image 151
Mitsubishi FR - S500 instruction manual 142