2.5 Current Detection Function Parameters

2.5.1 Output current detection functions

If the output remains higher than the Pr. 48 setting during inverter operation for longer than the time set in Pr. 49, the output current detection signal (Y12) is output from the inverter's open collector output terminal.

Output current detection

signal (Y12) OFF

currentOutput

 

Pr.48

 

 

 

 

 

 

100ms

ON OFF

Pr.49

Time

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

48

Output current detection

150%

0 to 200%

 

level

Setting is enabled when

 

 

 

49

Output current detection

0s

0 to 10s

Pr. 30 = "1"

signal delay time

 

 

 

 

 

<Setting>

Parameter

Description

Number

 

48Set the output current detection level.

100% is the rated inverter current.

Set the output current detection time. Set the time from when the output

49current has risen above the Pr. 48 setting until the output current detection signal (Y12) is output.

CAUTION

Once turned on because the current has risen above the preset detection level, the output current detection signal is held on for at least 100ms (approximately).

Using Pr. 64 or Pr. 65 to change terminal assignment may affect the other functions. Make setting after confirming the function of each terminal.

Related parameters

Assignment of Y12 signal to terminal Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C terminal function selection" (refer to page 90)