Item

Power supply voltage (V1)

Power supply side current

(I1)

Power supply side power

(P1)

Power supply side power factor (Pf1)

Output side voltage (V2)

Output side current (I2)

Output side power (P2)

Output side power factor

(Pf2)

Converter output

Frequency setting signal

Measuring Points and Instruments

Measuring Point

Measuring

Remarks

Instrument

(Reference Measured Value)

 

 

 

 

Is the commercial power supply

Across R-S, S-T

Moving-iron type

within permissible variation of AC

and T-R

AC voltmeter

voltage

 

 

 

(Refer to page 161)

R, S and T line

Moving-iron type

 

currents

AC ammeter

 

At R, S and T, and

Electrodynamic

 

P1 = W11 + W12 + W13

 

across R-S, S-T

type single-phase

 

 

(3-wattmeter method)

and T-R

wattmeter

 

 

 

Calculate after measuring power supply voltage, power supply side current and power supply side power.

[For three-phase power supply]

[For single-phase power supply]

P1

 

 

 

 

 

 

P1

 

 

 

 

 

 

 

 

 

 

 

Pf1= 3V1

 

 

I1

 

 

100%

Pf1= V1

 

I1

 

100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rectifier type AC

 

 

 

 

 

 

 

Across U-V, V-W

 

 

voltmeter (Note 1)

 

Difference between phases is

 

 

(Cannot be

 

within ± 1% of maximum output

and W-U

 

 

 

 

 

measured by

 

voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

moving-iron type)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moving-iron type

 

Current should be equal to or

U, V and W line

 

 

 

less than rated inverter current.

 

 

AC ammeter

 

currents

 

 

 

Difference between phases is

 

 

(Note 2)

 

 

 

 

 

 

 

 

 

 

10% or lower.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

At U, V and W, and

Electrodynamic

 

P2 = W21 + W22

across U-V and V-

type single-phase

 

2-wattmeter method (or 3-

W

 

 

wattmeter

 

wattmeter method)

Calculate in similar manner to power supply side power factor.

P2

 

 

 

 

 

 

 

 

 

 

 

Pf2= 3V2

 

I2

 

 

100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Across P-N

 

 

Moving-coil type

 

Inverter LED display is lit.

 

 

 

 

 

(such as a meter)

 

1.35 × V1

 

 

 

 

 

 

 

 

 

 

 

 

 

Across 2 (+)-5

 

 

Moving-coil type

 

0 to 5V/0 to 10VDC

is"5" common.

 

 

 

 

 

 

 

 

(Meter, etc. may be

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Across 4 (+)-5

 

 

used)

 

4 to 20mADC

 

 

 

 

(Internal resistance:

 

 

 

 

 

 

 

 

 

 

50kor larger)

 

 

 

 

 

 

 