<When single-phase power input is provided for three-phase power input inverter (NA version only)>

Reduce the output current.

FR-S520- K-NA inverter

0.1

0.2

0.4

0.75

1.5

2.2

3.7

Rated output current (A)

0.4

0.8

1.5

2.5

4.0

5.0

7.0

Power supply capacity (kVA)

0.4

0.8

1.5

2.5

4.5

5.5

9.0

AC input current (A)

1.1

2.4

4.5

6.4

11.2

12.9

17.4

Set m9 (Pr. 637) "current detection filter".

Setting "801" in the manufacturer setting parameter C8 enables you to set the m9 parameter.

CAUTION

Parameters other than m9 can also be made to be displayed, but never alter these since they are manufacturer setting parameters.

m9 Setting

Description

0

Single-phase power input

- - -

Three-phase power input

(Factory setting)

 

CAUTION

Always return the C8 parameter to 0 (factory setting) after you have finished the setting of m9.

6

Page 15
Image 15