<Set point input calibration>

1.Apply the input voltage of 0% set point setting (e.g. 0V) across terminals 2-5.

2.Make calibration using the calibration parameters C2, C3. At this time, enter in C2 the frequency which should be output by the inverter at the deviation of 0% (e.g. 0Hz). (When using the FR-PU04, make calibration with Pr. 902.)

3.Apply the voltage of 100% set point (e.g. 5V) to across terminals 2-5.

4.Make calibration using Pr. 38 and calibration parameter C4. At this time, enter in Pr. 38 the frequency which should be output by the inverter at the deviation of 100% (e.g. 60Hz). (When using the FR-PU04, make calibration with Pr. 903.)

<Detector output calibration>

1.Apply the output current of 0% detector setting (e.g. 4mA) across terminals 4-5.

2.Make calibration using the calibration parameter C6. (When using the FR-PU04, make calibration with Pr. 904.)

3.Apply the output current of 100% detector setting (e.g. 20mA) across terminals 4-5.

4.Make calibration using the calibration parameter C7. (When using the FR-PU04, make calibration with Pr. 905.)

Note: The frequencies set in the calibration parameter C5 and Pr. 39 should be equal to those set in the calibration parameter C2 and Pr. 38, respectively.

The results of the above calibration are as shown below:

 

[Set point setting]

 

 

 

[Detection value]

 

[Manipulated variable]

 

 

 

 

 

 

 

 

 

Manipulated

 

 

(%)

 

 

 

 

(%)

 

 

 

variable (Hz)

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

100

 

 

 

60

 

 

 

0

 

 

 

 

0

 

 

 

0

 

 

 

0

5

(V)

0 4

20 (mA)

0

100 Deviation (%)

REMARKS

If the multi-speed (RH, RM, RL) signal or jog operation (jog) signal is entered, PID control is stopped and multi-speed or jog operation is started.

When the terminal functions are changed using Pr. 60 to Pr. 65, the other functions may be affected. Confirm the functions of the corresponding terminals before making settings.

When PID control is selected, the minimum frequency is the frequency set in the calibration parameter C2 and the maximum frequency is the frequency set in Pr. 38. (The Pr. 1 "maximum frequency" and Pr. 2 "minimum frequency" settings are also valid.)

Related parameters

X14 signal assignment Pr. 60 to Pr. 63 (input terminal function selection) (refer to page 88) FUP, FDN and RL signal assignment Pr. 64 "RUN terminal function selection", Pr. 65 "A, B,

C terminal function selection" (refer to page 90)

Voltage input selection (0 to ±5V, 0 to ±10V) Pr. 73 "0-5V/0-10V selection" (refer to page 93) Operation mode selection Pr. 79 "operation mode selection" (refer to page 98)

Making terminal calibration Pr. 38, Pr. 39, C2 to C7 (calibration parameters) (refer to page 74)

108

Page 117
Image 117
Mitsubishi FR - S500 instruction manual Set point input calibration, Detector output calibration, 108