E6581301

10.6Connection of a DC power supply and other electric units

Besides a three-phase commercial power supply, a single-phase 200V power supply (5.5kW or less) and a DC power supply can be connected to the VFAS1 inverter.

When connecting each of these units, keep in mind the points described in the following sections.

10.6.1 Connection of a single-phase 200V power supply

The table below shows which model to select when operating a three-phase induction motor, using a single-phase 200V power supply (200-240V, 50/60Hz).

Input power

Applicable motor (kW)

Inverter type

Single phase

0.4

VFAS1-2007PL

200~240V

0.75

VFAS1-2015PL

50/60Hz

1.5

VFAS1-2022PL

 

2.2

VFAS1-2037PL

 

3.7

VFAS1-2055PL

 

5.5

VFAS1-2075PL

Note: Set the parameter ￿￿￿￿ to ￿ (input phase failure detection mode selection: disabled).

10.6.2 When using the inverter along with a DC power supply!

Keep the following in mind when connecting a DC power supply to the VFAS1 (PA/+ and PC/- terminals).

Note 1: An optional initial charger (MCR-2550) is needed for middle- and large-capacity models.

Note 2: 200V-75kW and 400V-110kW or more models are needed to change the connecting for the cooling fan.

Note 3: A DC reactor does not need to be connected to the inverter.

￿For details about use in combination with a DC power supply, refer to the instruction manual (E6581432) specified in section 6.42.

 

 

Voltage class

Inverter model

Initial charger (optional)

Change to connection of

DC reactor

 

 

cooling fan power supply

 

 

 

 

 

 

 

 

 

VFAS1-2004PL~

No required

No required

No required

 

 

 

VFAS1-2150PM

 

 

 

 

 

 

 

 

200V class

VFAS1-2185PM~

MCR-2550×1

No required

No required

 

 

 

VFAS1-2550P

 

 

 

 

 

 

10

 

 

VFAS1-2750P

MCR-2550×2 (parallel)

Required

No required

 

 

VFAS1-4007PL~

No required

No required

No required

 

 

 

VFAS1-4185PL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VFAS1-4220PL~

MCR-2550×1

No required

No required

 

 

 

VFAS1-4900PC

 

 

 

 

 

 

 

 

 

VFAS1-4110KPC

MCR-2550×1

Required

No required

 

 

400V class

VFAS1-4132KPC~

MCR-2550×2 (parallel)

Required

No required

 

 

 

VFAS1-4220KPC

 

 

 

 

 

 

 

 

 

VFAS1-4280KPC

MCR-2550×3 (parallel)

Required

No required

 

 

 

VFAS1-4355KPC,

MCR-2550×4 (parallel)

Required

No required

 

 

 

VFAS1-4400KPC

 

 

 

 

 

 

 

 

 

VFAS1-4500KPC

MCR-2550×5 (parallel)

Required

No required

 

 

Note: Set the parameter ￿￿￿￿ to ￿ (input phase failure detection mode selection: disabled).

 

J-12

Page 252
Image 252
Toshiba VF-AS1 Connection of a DC power supply and other electric units, Connection of a single-phase 200V power supply