10.6 Connection of a DC power supply and other electric units
Besides a three-phase commercial power supply, a single-phase 200V power sup ply (5.5kW or less) and a DC power
supply can be connected to the VFAS1 inverter.
When connecting each of these units, keep in mind the points descri bed in the following sections.

10.6.1 Connection of a single-phase 200V pow er supply

The table below shows which model to select when operating a three -phase induction motor, using a single-phase
200V power supply (200-240V, 50/60Hz).
Input power Applicable motor (kW) Inverter type
Single phase
200~240V
50/60Hz
0.4 VFAS1-2007PL
0.75 VFAS1-2015PL
1.5 VFAS1-2022PL
2.2 VFAS1-2037PL
3.7 VFAS1-2055PL
5.5 VFAS1-2075PL
Note: Set the parameter
H
to
(input phase failure detection mode selection: disabled).

10.6.2 When using the inverter along w ith a DC power supply!

!!
!
Keep the following in mind when connecting a DC power supply to the VFAS1 (PA/+ and PC/- terminals).
Note 1: An optional initial charger (MCR-2550) is needed for middle- and l arge-capacity models.
Note 2: 200V-75kW and 400V-110kW or more models are needed to change the connecting for the cooling fan.
Note 3: A DC reactor does not need to be connected to the inverter.
For details about use in combination with a DC power supply, refer to the instr uction manual (E6581432) specified
in section 6.42.
Voltage class Inverter model Initial charger (optional) Change to connection of
cooling fan power supply DC reactor
200V class
VFAS1-2004PL~
VFAS1-2150PM No required No required No required
VFAS1-2185PM~
VFAS1-2550P MCR-2550×1 No required No required
VFAS1-2750P MCR-2550×2 (parallel) Required No required
400V class
VFAS1-4007PL~
VFAS1-4185PL No required No required No required
VFAS1-4220PL~
VFAS1-4900PC MCR-2550×1 No required No required
VFAS1-4110KPC MCR-2550×1 Required No required
VFAS1-4132KPC~
VFAS1-4220KPC MCR-2550×2 (parallel) Required No required
VFAS1-4280KPC MCR-2550×3 (parallel) Required No required
VFAS1-4355KPC,
VFAS1-4400KPC MCR-2550×4 (parallel) Required No required
VFAS1-4500KPC MCR-2550×5 (parallel) Required No required
Note: Set the parameter
H
to
(input phase failure detection mode selection: disabled).