E6581301

6.33.18 VI/II analog input wire breakage detection level!

￿￿￿￿

: VI/II analog input wire breakage detection level

• Function

The inverter will trip if the VI/II value remains below the specified value for 0.3 seconds or moreThe message “￿￿￿￿” is displayed.

￿￿￿￿=￿: Disabled ·········

The detection function is disabled.

 

 

￿￿￿￿=￿~￿￿￿ ··············

The inverter will trip if the VI/II value remains below the specified value for 0.3

 

 

seconds or more.

 

 

 

 

 

 

 

Title

 

Function

Adjustment range

Default setting

￿￿￿￿

VI/II analog input wire breakage detection level

￿:None

￿￿

￿~￿￿￿ %

 

 

 

 

6.33.19 Guide to time of replacement!

￿￿￿￿

: Annual average ambient temperature

• Function

You can set the inverter so that it will calculate the remaining useful life of the cooling fan, main circuit capacitor and on-board capacitor from the ON time of the inverter, the operating time of the motor, the output current (load factor) and the setting of ￿￿￿￿ and that it will display and send out an alarm through output terminals when each component is approaching the end of its useful life.

6

 

 

 

 

 

 

Title

Function

Adjustment range

Default setting

 

 

 

 

 

 

￿: -10~+10°C

 

 

 

 

 

￿: +11~+20°C

 

 

 

￿￿￿￿￿

Annual average ambient temperature

￿: +21~+30°C

￿￿

 

 

￿: +31~+40°C

 

 

 

 

 

 

 

 

 

￿: +41~+50°C

 

 

 

 

 

￿: +51~+60°C

 

Note 1: Using ￿￿￿￿, enter the annual average temperature around the inverter. Be careful not to enter the annual highest temperature.￿

Note 2: Set ￿￿￿￿ at the time of installation of the inverter, and do not change its setting after the start of use. Changing the setting may cause a part replacement alarm calculation error.￿

6.33.20Rush current suppression relay activation time

￿￿￿￿￿: Rush current suppression relay activation time

• Function

This parameter is used to control the rush current suppressing resistor shorting relay when a direct current is passed or multiple inverters are used with their DC sections connected to each other.

Title

Function

Adjustment range

Default setting

￿￿￿￿￿

Rush current suppression relay

￿￿￿~￿￿￿ sec.

￿￿￿￿

activation time

 

 

 

The rush current suppressing relay is activated on the expiration of the time limit set with parameter ￿￿￿￿ after the voltage in the DC section of the inverter has reached the specified level.

F-66

Page 182