13.2Method of resetting causes of trip

Do not reset the inverter when tripped because of a failure or error before eliminating the cause. Resetting the tripped inverter before eliminating the problem causes it to trip again.

For recovering inverter from trip status,

(1)By turning off the power (Keep the inverter off until the LED turns off.)

￿Refer to Section 6.33.2 (inverter trip retention selection ￿￿￿￿) for details.

(2)By means of an external signal (shorting RES and CC on control terminal board release)

(3)By operation panel operation

(4)By means of a communication

￿For details, refer to the instruction manual for the communications device used specified in section 6.41.

reset it in one of the following ways.

To reset the inverter by operation panel operation, follow these steps.

1.Check whether the LED on the control panel indicates that tripping has occurred. If the occurrence of tripping is not indicated, press the MODE key to display it.

2.Press the STOP key and make sure that ￿￿￿ is displayed.

3.Pressing the STOP key again will reset the inverter if the cause of the trip has already been eliminated.

"When any overload function [￿￿￿: Inverter overload, ￿￿￿: Motor overload, ￿￿￿: Dynamic braking resistor overload] is active, the inverter cannot be reset by inputting a reset signal from an external device or by operation panel operation before the virtual cooling time has passed.

Standard virtual cooling time! …! In case of ￿￿￿: for about 30 seconds after trip

In case of ￿￿￿: for about 120 seconds after trip

In case of ￿￿￿: for about 20 seconds after trip

Note: ￿￿￿ or ￿￿￿ can be reset during virtual cooling time if the CPU1 version is Ver.106 or successor. However, note that the inverter is in a state easy to trip during virtual cooling time.

"If the inverter trips because of overheat (￿￿), reset it after a considerably long time enough for cooling it down completely, because overheat is detected based on its internal temperature.

- Caution -

For quickly recovering inverter from trip status, turn it off once and reset it. However, this measure is taken frequently, it may cause damage to the motor and other component units.