8.2.2 Display of detailed information on a past trip

Details on a past trip (of trips 1 to 4) can be displayed, as shown in the table below, by pressing the ENT key when the trip record is selected in the status monitor mode.

Unlike the " Monitor display at tripping " in 8.4.2, details on a past trip can be displayed, even after the inverter is turned off or reset.

[Note 5]

[Note 1]

[Note 2]

[Note 2] [Note 3]

[Note 2]

[Note 4]

[Note 6]

Item displayed

Key

LED display

Description

operated

 

 

 

Past trip 1

 

"￿￿￿￿

Past trip 1 (displayed alternately.)

Continuous trips

ENT

￿￿￿￿￿

The number of time the same trip occurred in succession is displayed.

 

 

 

("￿￿￿, "￿￿￿, "￿￿￿, "￿￿￿ Unit: times)

Output frequency

 

￿￿￿￿

The operation frequency when the trip occurred is displayed.

 

 

 

 

Status monitor mode

 

￿￿￿￿￿

The direction of rotation is displayed. (￿:Forward run, ￿:Reverse run)

(Rotating direction)

 

 

 

 

 

 

 

 

Frequency command

 

￿￿#￿￿

The operation frequency command value is displayed.

value

 

(When ￿￿￿￿=￿, Frequency command)

 

 

Output current

 

￿￿￿￿￿

The inverter output current (load current) is displayed.

 

 

 

(When ￿￿￿￿=￿, Output current)

Input voltage (DC

 

￿￿￿￿￿

The inverter DC voltage is displayed. (Default setting unit: %)

detection)

 

 

(When ￿￿￿￿=￿, Input voltage) [Note 3]

Output voltage

 

￿￿￿￿￿

The inverter output voltage is displayed. (Default setting unit: %)

 

 

 

(When ￿￿￿￿=￿, output voltage)

Input terminal

 

!!!!!!!!￿

The ON/OFF status of each of the control signal input terminals (F, R,

information

 

 

ST, RES, S1, S2, S3, RR/S4) is displayed in bits.

Output terminal

 

￿￿￿￿￿￿￿￿

The ON/OFF status of each of the control signal output terminals

information

 

 

(OUT1, OUT2, FL) is displayed in bits.

Cumulative operation

 

￿$￿￿￿

The cumulative operation time when the trip occurred is displayed.

time

 

 

(0.01=1 hour, 1.00=100 hours)

Past trip 1

MODE

"￿￿ ￿

Press this key to return to past trip 1.

 

 

 

 

Note 1: Press the

or

key to change items displayed in the status monitor mode.

8

 

Note 2: You can switch between % and A (ampere)/V (volt), using the parameter %&￿￿ (current/voltage unit

 

 

selection).

 

 

 

Note 3: The input voltage displayed is 1/ 2 times as large as the rectified DC input voltage.

 

Note 4: The number of bars displayed varies depending on the setting of ￿￿￿ (logic output/pulse train output

 

selection). The bar representing the OUT1 terminal is displayed only when logic output function is assigned to it.

 

If ￿￿￿ =￿

:The bar representing OUT1 is displayed.

 

If ￿￿￿ =￿

:The bar representing OUT1 is not displayed.

 

Note 5: If there is no trip record, ￿￿￿￿ is displayed.

Note 6: The cumulative operation time increments only when the machine is in operation.

H-5

Page 223
Image 223
Toshiba VF-AS1 Display of detailed information on a past trip, Unit times, Press this key to return to past trip