! E6581301

J-3

10
Selection of wiring equipment
Voltage
class
Applicable
motor [kW] Inverter model
Input current[A]
Molded Case Circuit B reaker
(MCCB)
Magnetic contactor
(MC)
Without
Reactor
With
Reactor
Without
Reactor
With
Reactor
Without
Reactor
With
Reactor
Rated current
[A]
Rated current
[A]
Operationl
current [A]
AC-1
Operationl
current [A]
AC-1
200V
class
0.4 VFAS1-2004PL 3.5 2.1 5 5 25 25
0.75 VFAS1-2007PL 6.1 3.2 10 5 25 25
1.5 VFAS1-2015PL 11.3 6.4 15 10 25 25
2.2 VFAS1-2022PL 15 9.3 20 15 25 25
3.7/4.0 VFAS1-2037PL 25.8 15.5 30 30 32 25
5.5 VFAS1-2055PL 35 22. 5 50 40 40 25
7.5 VFAS1-2075PL 45 34.5 60 40 50 40
11 VFAS1-2110PM - 53.3 - 75 - 80
15 VFAS1-2150PM -!71.7 -!100 -!80
18.5 VFAS1-2185PM -!77 -!100 -!80
22 VFAS1-2220PM -!88 -!125 -!125
30 VFAS1-2300PM -!124 -!150 -!125
37 VFAS1-2370PM -!141 -!175 -!250
45 VFAS1-2450PM -!167 -!200 -!250
55 VFAS1-2550P -!200 -!250 -!275
75 VFAS1-2750P -!271 -!350 -!350
400V
class
0.75 VFAS1-4007PL 3.7 2.1 5 4 25 25
1.5 VFAS1-4015PL 5.8 3.8 10 6.3 25 25
2.2 VFAS1-4022PL 8.2 5.7 14 10 25 25
3.7/4.0 VFAS1-4037PL 14.1 8.7 18 14 25 25
5.5 VFAS1-4055PL 20.3 12.7 32 25 25 25
7.5 VFAS1-4075PL 27 16.3 32 25 32 25
11 VFAS1-4110PL 36.6 21.5 50 30 40 32
15 VFAS1-4150PL 48 33.5 60 40 50 40
18.5 VFAS1-4185PL - 45.5 - 60 - 50
22 VFAS1-4220PL -!50 -!60 -!50
30 VFAS1-4300PL -!66 -!100 -!80
37 VFAS1-4370PL -!84 -!100 -!125
45 VFAS1-4450PL -!104 -!125 -!125
55 VFAS1-4550PL -!120 -!150 -!125
75 VFAS1-4750PL -!167 -!200 -!250
90 VFAS1-4900PC -!166 -!200 -!250
110 VFAS1-4110KPC -!202 -!250 -!275
132 VFAS1-4132KPC -!238 -!300 -!315
160 VFAS1-4160KPC -!289 -!350 -!350
200 VFAS1-4200KPC -!356 -!500 -!500
220 VFAS1-4220KPC -!396 -!500 -!500
280 VFAS1-4280KPC -!494 -!700 -!700
355 VFAS1-4355KPC -!636 -!1000 -!1000
400 VFAS1-4400KPC -!707 -!1000 -!1000
500 VFAS1-4500KPC -!875 -!1200 -!1600
(*1): Selections for use of the Toshiba 4-pole standard motor with power su pply voltage of 200V/400V-50Hz.
(*2): Choose the MCCB according to the power supply capacity.
For comply with UL and CSA standard, use the fuse certified by UL and CSA.
(*3): When using on the motor side during commercial-power supply operati on, choose the MC with class AC-3 rated curre nt
for the motor rated current.
(*4): Attach surge killers to the magnetic contactor and exciting coil of the relay.
(*5): In the case the magnetic contactor (MC) with 2a-type auxiliary contacts i s used for the control circuit, raise the rel iability
of the contact by using 2a-type contacts in parallel connection.
(*6): For 200V/55kW model and larger and 400V/90kW model and larger, be sure to i nstall a DC reactor.