E6581301

Selection of wiring equipment

 

 

 

 

 

Molded Case Circuit Breaker

Magnetic contactor

 

 

 

 

 

Input current[A]

(MCCB)

(MC)

 

 

Voltage

Applicable

 

Without

With

Without

With

 

 

 

 

 

 

 

Inverter model

 

 

Reactor

Reactor

Reactor

Reactor

 

 

class

motor [kW]

 

 

 

 

 

 

 

Without

With

Rated current

Rated current

Operationl

Operationl

 

 

 

 

 

current [A]

current [A]

 

 

 

 

 

Reactor

Reactor

[A]

[A]

 

 

 

 

 

AC-1

AC-1

 

 

 

 

 

 

 

 

 

 

 

 

0.4

VFAS1-2004PL

3.5

2.1

5

5

25

25

 

 

 

0.75

VFAS1-2007PL

6.1

3.2

10

5

25

25

 

 

 

1.5

VFAS1-2015PL

11.3

6.4

15

10

25

25

 

 

 

2.2

VFAS1-2022PL

15

9.3

20

15

25

25

 

 

 

3.7/4.0

VFAS1-2037PL

25.8

15.5

30

30

32

25

 

 

 

5.5

VFAS1-2055PL

35

22. 5

50

40

40

25

 

 

 

7.5

VFAS1-2075PL

45

34.5

60

40

50

40

 

 

200V

11

VFAS1-2110PM

-

53.3

-

75

-

80

 

 

class

15

VFAS1-2150PM

-!

71.7

-!

100

-!

80

 

 

 

18.5

VFAS1-2185PM

-!

77

-!

100

-!

80

 

 

 

22

VFAS1-2220PM

-!

88

-!

125

-!

125

 

 

 

30

VFAS1-2300PM

-!

124

-!

150

-!

125

 

 

 

37

VFAS1-2370PM

-!

141

-!

175

-!

250

 

 

 

45

VFAS1-2450PM

-!

167

-!

200

-!

250

 

 

 

55

VFAS1-2550P

-!

200

-!

250

-!

275

 

 

 

75

VFAS1-2750P

-!

271

-!

350

-!

350

 

 

 

0.75

VFAS1-4007PL

3.7

2.1

5

4

25

25

 

 

 

1.5

VFAS1-4015PL

5.8

3.8

10

6.3

25

25

 

 

 

2.2

VFAS1-4022PL

8.2

5.7

14

10

25

25

 

 

 

3.7/4.0

VFAS1-4037PL

14.1

8.7

18

14

25

25

 

 

 

5.5

VFAS1-4055PL

20.3

12.7

32

25

25

25

 

 

 

7.5

VFAS1-4075PL

27

16.3

32

25

32

25

 

 

 

11

VFAS1-4110PL

36.6

21.5

50

30

40

32

 

 

 

15

VFAS1-4150PL

48

33.5

60

40

50

40

 

 

 

18.5

VFAS1-4185PL

-

45.5

-

60

-

50

 

 

 

22

VFAS1-4220PL

-!

50

-!

60

-!

50

 

 

 

30

VFAS1-4300PL

-!

66

-!

100

-!

80

 

 

400V

37

VFAS1-4370PL

-!

84

-!

100

-!

125

 

 

45

VFAS1-4450PL

-!

104

-!

125

-!

125

 

 

class

 

 

55

VFAS1-4550PL

-!

120

-!

150

-!

125

 

 

 

 

 

 

75

VFAS1-4750PL

-!

167

-!

200

-!

250

 

10

 

90

VFAS1-4900PC

-!

166

-!

200

-!

250

 

 

110

VFAS1-4110KPC

-!

202

-!

250

-!

275

 

 

 

 

 

132

VFAS1-4132KPC

-!

238

-!

300

-!

315

 

 

 

160

VFAS1-4160KPC

-!

289

-!

350

-!

350

 

 

 

200

VFAS1-4200KPC

-!

356

-!

500

-!

500

 

 

 

220

VFAS1-4220KPC

-!

396

-!

500

-!

500

 

 

 

280

VFAS1-4280KPC

-!

494

-!

700

-!

700

 

 

 

355

VFAS1-4355KPC

-!

636

-!

1000

-!

1000

 

 

 

400

VFAS1-4400KPC

-!

707

-!

1000

-!

1000

 

 

 

500

VFAS1-4500KPC

-!

875

-!

1200

-!

1600

 

 

(*1): Selections for use of the Toshiba 4-pole standard motor with power supply voltage of 200V/400V-50Hz.

(*2): Choose the MCCB according to the power supply capacity.

For comply with UL and CSA standard, use the fuse certified by UL and CSA.

(*3): When using on the motor side during commercial-power supply operation, choose the MC with class AC-3 rated current for the motor rated current.

(*4): Attach surge killers to the magnetic contactor and exciting coil of the relay.

(*5): In the case the magnetic contactor (MC) with 2a-type auxiliary contacts is used for the control circuit, raise the reliability of the contact by using 2a-type contacts in parallel connection.

(*6): For 200V/55kW model and larger and 400V/90kW model and larger, be sure to install a DC reactor.

J-3