E6581301!

B-13

2
Terminal
symbol
Input/
output Function (Sink Source logic) Electrical
specifications Inverter internal circuits
+SU
Input
DC power input terminal for operating the
control circuit. Connect a control power backup
device (optional) between +SU and CC.
Voltage:24Vdc±10%
Use a power supply
with a current rating
of 1.05A or more.
(In case of not install
options, current rating
is 300mA )
FLA
FLB
FLC
Output
Relay contact output. Contact rating
Used to detect the activation of the inverter's
protective function. Contact across FLA-FLC is
closed and FLB-FLC is opened during
protection function operation.
250Vac-2A
30Vdc-1A
:at resistance load
250Vac-1A
:cosφ=0.4
l
SW SW settings
Default setting
(Settings marked
with Ɣ)
Function
SW1
Ɣ
(-H1,HN,WN)
Setting for using the inverter’s internal power supply in sink log ic
mode
Setting for using the inverter’s e xternal power supply in sink logic
mode
Ɣ
(-WP) Setting for operating the inverter in source logic mode
SW2
ƔSetting for using the analog output terminal FM to output current
of 0-1mA
Setting for using the analog output terminal FM to output current
of 0-10V or 0-20mA (4-20mA)
0-10V (H=) or 0-20mA (H=) can be selected by
changing parameter settings.
SW3
ƔSetting for using the input terminal RR/S4 as an analog input
terminal (0-10Vdc)
Setting for using the input terminal RR/ S4 as a contact input
terminal
SW4
Ɣ
Setting for using the output terminal OUT1 as a logic output
terminal
When turning the switch to this position, always set the
parameter H to (logic output).
Setting for using the output terminal OUT1 as a pulse output
terminal
When turning the switch to this position, always set the
parameter H to (pulse output).
S
OURCE
S
INK
PLC
INT/PLC
INT
S
OURCE
S
INK
PLC
INT/PLC
INT
S
OURCE
S
INK
PLC
INT/PLC
INT
!
-
10V
0-20mA
-
1mA
!
FM
!
!
-
10V
0-20mA
-
1mA
!
FM
!
S4
RR/S4
RR
S4
RR/S4
RR
"#$%
$&
&#'(
PULS
Lo
OUT1

!

P24
!
FL
!
FLA
!
FLB
!
FLC
!

!

P24
1
+SU
CC