E6581301

4)Setting the run, stop and operation frequencies (forward run, reverse run and coast stop) by means of external signals (default setting)

Title

Function

Example of setting

￿￿￿￿

Command mode

￿:(Terminal input)

selection

 

 

 

 

￿(VI/II (voltage/current input) )

 

Frequency

￿(RR/S4

￿￿￿￿

setting mode

(potentiometer/voltage

 

selection 1

input) )

 

 

￿(RX (voltage input) )

Run/stop :ON/OFF of terminals F-CC/R-CC Speed command :External signal input

(1)VI/II terminal: 0~+10Vdc (0~+5Vdc) or 4(0)~20mAdc

(2)RR/S4 terminal: Potentiometer 0~+10Vdc (0~+5Vdc)

(3)RX terminal: 0~±10Vdc (0~±5Vdc)

«Example of a connection diagram: SW1 set to sink logic»

5

 

 

 

 

Motor

Power

R/L1

 

U/T1

IM

supply

S/L2

 

V/T2

T/L3

 

W/T3

 

 

 

 

 

 

F

ON:Forward run,

 

 

 

OFF:Deceleration stop

 

 

 

 

 

Inverter

R

ON:Reverse run,

 

OFF:Deceleration stop

 

 

 

 

 

 

 

ST

ON:Standby,

 

 

 

OFF:Coast stop

 

 

 

 

 

 

 

CC

 

 

CCA

RX VI/II

RR/S4 PP

 

 

 

 

+

(3) 0~±10Vdc

 

 

 

-

(0~±5Vdc)

 

 

 

+

(1) 0~+10Vdc

 

 

 

-

(0~+5Vdc)

 

 

 

 

or 4(0)~20mAdc

 

(2) External potentiometer

 

!The inverter is factory-configured so that, if F and R are turned on at the same time, the inverter will stop operation. If necessary, the direction of rotation can be reversed by changing parameter settings.

￿ Refer to Section 6.2.1.

*Other speed setting

￿: 2-wire RS485 input

￿: 4-wire RS485 input enabled

￿: Communication option input enabled *

￿: Optional AI1 (Differential current input) *

:Optional AI2 (voltage/current input) *

￿￿: Motor operated pot mop setting

￿￿: RP pulse input *

￿￿: High-speed pulse input *

￿￿: -

*Commands marked with * are optional. Refer to Instruction Manual of options described in Section 10.