E6581301

 

 

 

3) Common specification

 

 

 

 

 

 

Item

Specification

 

 

 

 

 

Control system

Sinusoidal PWM control

 

 

 

 

 

Output voltage adjustment

Main circuit voltage feedback control. (Switchable between automatic adjustment/fix/control off)

 

 

 

 

 

Output frequency range

Setting between 0.01 to 500Hz. Default max. frequency is set to 0.01 to 60Hz.

 

 

 

 

 

Maximum frequency adjustment (30 to 500Hz)

 

 

 

 

 

 

 

 

 

 

 

Minimum setting steps of

0.01Hz: operation panel input (60Hz base),

 

 

 

 

 

frequency

0.03Hz: analog input (60Hz base, 11 bit/0 to 10Vdc)

 

 

 

 

 

Frequency accuracy

Analog input: ±0.2% of the maximum output frequency (at 25±10°C)

 

 

 

 

 

Digital input: ±0.01%±0.022Hz of the output frequency

 

 

 

 

 

 

 

 

 

 

Control

Voltage/frequency

V/f constant, square reduction torque control, automatic torque boost, vector calculation control, base

 

 

 

 

(0 to 30%), start frequency adjustment (0 to 10Hz), stop frequency adjustment (0 to 30Hz)

 

 

 

 

 

characteristics

frequency adjustment 1, 2, 3, and 4 (25 to 500Hz), V/f 5-point arbitrary setting, torque boost adjustment

 

 

 

 

 

 

 

 

 

 

specification

 

 

 

 

 

 

 

3k￿ potentiometer (possible to connect to 1 to 10k￿-rated potentiometer)

 

 

 

 

 

 

 

 

 

 

 

Frequency setting signal

0 to 10Vdc (input impedance Zin: 30k￿)

 

 

 

 

 

0 to ±10Vdc (Zin: 22k￿)

 

 

 

 

 

 

 

 

 

 

 

 

4 to 20mAdc (Zin:242￿)

 

 

 

 

 

Terminal board base

The characteristic can be set arbitrarily by two-point setting. Compliant with 6 types of input; analog input

 

 

 

 

 

frequency

(RR, VI/II, RX, AI1, AI2), and pulse input. (*AI1, AI2, pulse input: optional)

 

 

 

 

 

Frequency jump

3 places. Setting of jump frequency and width.

 

 

 

 

 

Upper and lower limit

Upper limit frequency: 0 to max. frequency, lower limit frequency: 0 to upper limit frequency

 

 

 

 

 

frequencies

 

 

 

 

 

 

PWM carrier frequency

200V-45kW or less, adjustable between 1.0 to 16kHz for 400V-75kW or less

 

 

 

 

 

200V-55kW or less, adjustable between 2.5 to 8kHz for 400V-90kW or more

 

 

 

 

 

 

 

 

 

 

 

PID control

Adjustment of proportional gain, integral time, differential time and delay filter

 

 

 

 

 

Torque control

Voltage command input specification: DC 0 to ±10V

 

 

 

 

 

Acceleration/deceleration

0.01 to 6000 sec. Selectable from among acceleration/deceleration. times 1, 2, 3 and 4. Automatic

 

 

 

 

 

time

acceleration/deceleration function. S-pattern acceleration/deceleration 1 and 2 pattern adjustable.

 

 

 

 

 

DC braking

Adjustment of braking start frequency (0 to 120Hz), braking (0 to 100%) and braking time (0 to 20 sec.).

 

 

 

 

 

With emergency stop braking function and motor shaft fix control function.

 

 

 

 

 

 

 

 

 

 

 

Forward run/reverse run

With F-CC closed to forward run, with R-CC closed to reverse run, with both closed to reverse run. With

 

 

 

 

 

[Note 1]

ST-CC opened to coast stop. Emergency stop by panel operation or terminal board.

 

 

 

 

 

Jog run

Jog mode, if selected, allows jog operation from the operation panel

 

 

 

 

 

[Note 1]

Jog run operation by terminal board is possible by setting the parameters.

 

 

 

 

 

Preset speed operation

By changing the combination of open/close between S1, S2, S3, RR/S4-CC, set frequency + 15-speed

 

 

 

 

 

operation.

 

 

 

 

 

[Note 1]

 

 

 

 

Operation

Selectable between acceleration/deceleration time, torque limit and V/f by set frequency.

 

 

 

 

 

 

 

 

 

Soft stall

Automatic load reduction control at overloading. (Default: OFF)

 

 

 

 

 

Retry

Capable of restarting after a check of the main circuit elements in case the protective function is

 

 

 

 

 

 

activated. Max. 10 times selectable arbitrarily. Waiting time adjustment (0 to 10 sec.)

 

 

 

 

specifications

 

 

 

 

 

 

Cooling fan ON/OFF

The cooling fan will be stopped automatically to assure long life when unnecessary.

 

 

 

 

 

Operation panel key

Key prohibition selectable between STOP key only, MODE key only, etc. All key operations can be

 

 

 

 

 

operation ON/OFF control

prohibited.

 

 

 

 

 

Regenerative power

Possible to keep the motor running using its regenerative energy in case of a momentary power failure.

 

 

 

 

 

ride-through control

(Default: OFF)

 

 

 

 

 

Auto-restart operation

Possible to restart the motor in coasting in accordance with its speed and direction. (Default: OFF)

 

 

 

 

 

Simplified pattern

Possible to select each 8 patterns in 2 groups from 15-speed operation frequency. Max. 16 types of

 

 

 

 

 

operation

operation possible. Terminal board operation/repeat operation possible.

 

 

 

 

 

Commercial inverter

Possible to switch operation by commercial power source or inverter

 

 

 

 

 

switching

 

 

 

 

 

 

Light-load high-speed

Increases the operating efficiency of the machine by increasing the rotational speed of the motor when it

 

 

 

 

 

operation

is operated under light load.

 

 

 

 

 

Drooping function

When two or more inverters are used to operate a single load, this function prevents load from

 

 

 

 

 

concentrating on one inverter due to unbalance.

 

 

 

 

 

 

 

 

 

 

 

Override function

External input signal adjustment is possible to the operation frequency command value.

 

 

 

 

Protective

 

Stall prevention, current limit, overcurrent, overvoltage, short circuit on the load side, ground fault on the

 

 

 

 

Protective function

load side [Note 5], undervoltage, momentary power failure (15ms or more), non-stop control at

 

 

 

 

 

momentary power failure, overload protection, arm overload at starting, overcurrent on the load side at

 

 

 

 

 

 

 

 

12

 

 

 

starting, overcurrent and overload at dynamic braking resistance, overheat, emergency stop

 

 

 

function

Electronic thermal

Switchable between standard motor/constant torque VF motor, adjustment of overload protection and

 

 

 

 

Reset by 1a contact closed (or 1b contact opened), or by operation panel. Or power source OFF/ON.

 

 

 

 

 

characteristic

stall prevention level.

 

 

 

 

 

Reset

This function is also used to save and clear trip records.

 

 

 

 

 

 

 

 

 

(Continued overleaf)

L-3